With the jumper on X300 the kit can be adapted to
the type of microphone.
•
With the jumper connecting pin 1 and pin 2 of X300,
a dynamic microphone can be connected to X301,
e.g. LBB9081 and LBB9082.
•
With the jumper connecting pin 2 and pin 3 of X300,
an electret condenser microphone can be connected
to X301. In this mode, pin 1 and pin 3 of X301 will
have a 12 V phantom power supply.
21.2.4 Control input/outputs (X107)
The remote call station kit provides an external
interface for one control input and five control outputs.
This external interface consists of a pin header with 14
positions (see the PCB for the pin numbering).
figure 21.6: LBB9081 connection diagram
figure 21.7: LBB9082 connection diagram
table 21.6: X301 technical data
Microphone input sensitivity:
-50 dBV
Input control range:
-7 to 8 dB
S/N:
min. 60 dB at default sensitivity
Headroom:
min. 30 dB at default sensitivity
Bandwidth:
340 to 14000 Hz
(-3 dB with respect to level at 1 kHz)
10k
Ω
10k
Ω
blue
black
red
white
black
(thick)
5
6
3
1
2
1
3
2
black
white
red
table 21.7: X107 connector details
Pin
Signal
1
PTT input contact
2
GND
3
Output 1, out (power indicator)
4
Output 1, in (power indicator)
5
Output 2, out (fault indicator)
6
Output 2, in (fault indicator)
7
Output 3, out (call indicator)
8
Output 3, in (call indicator)
9
Output 4, out (system priority indicator)
10
Output 4, in (system priority indicator)
11
Output 5, out (system emergency indicator)
12
Output 5, in (system emergency indicator)
13
GND
14
GND
Содержание Praesideo 3.5
Страница 1: ...Praesideo 3 5 Installation and User Instructions Digital Public Address and Emergency Sound System en ...
Страница 131: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 4 Amplifiers en 131 Part 4 Amplifiers ...
Страница 201: ...Bosch Security Systems 2011 02 2011 02 Installation and User Instructions 5 Call Stations en 201 Part 5 Call Stations ...
Страница 309: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 8 Software en 309 Part 8 Software ...
Страница 411: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 10 Events en 411 Part 10 Events ...
Страница 487: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 12 Appendices en 487 Part 12 Appendices ...
Страница 497: ......
Страница 498: ... Bosch Security Systems B V Data subject to change without notice 2011 02 ...