18
en | Installation
PAVIRO Call Stations
2018.04 | 04 | F01U306899
Bosch Security Systems
5
Installation
5.1
Delivery condition
The call stations are programmed with the following factory
functions and properties settings:
Parameters
Setting/description
CAN address
0 (disconnected)
CAN baud rate
10 kbit/s
CAN termination
off
Name
PVA-15CST / PVA-15ECS
Password
Setup menu password-protected,
password: 2222
Prechime
Off
Buzzer
On (acoustic warning signal)
Compressor
Off
Options
Alarm buttons
Not configured
Key switch
Not configured
External
microphone
Not configured
Button
assignme
nt
Selection
buttons 1-n
Selection of zone 1 through n
(button 1 = zone 1, button 2 =
zone 2 etc.)
↵
Call in selected zones/groups,
default priority 50
▲
Switches system on/off, default
priority 40
▼
Stops an active audio signal,
default priority 69