Service Manual
Bosch IDS 2.0
| 41
Bosch Thermotechnology Corp.
|
07.2021
Data subject to change
Limited Condition
Status code
Fault Code
Fault Code Description
Potential Cause
P2/H5
Low pressure protection.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Under charged
C**
P3
Compressor over current protection.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Over charged.
Control board or compressor issue
d**
P4
High compressor discharge temperature (T5) protection.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Over charged
L**
P5
Condenser coil temperature (T3) protection in cooling.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Over charged
P8
DC outdoor fan motor protection.
Severe weather (fan running in standby mode due to
high wind)
PH
Low discharge superheat protection.
Poor heat exchange on coil
Fan motor failure
Service valves not open
TXV/EEV/filter drier blocked
Under charged
L0-L9
The IPM module protection.
Control board failed
Compressor failed
Abnormal pressure
AtL
Ambient Temperature Limited Condition.
Ambient temperature beyond operating range
Incorrect O/B thermostat setting
T4 sensor fault
P**
Running indication under compressor ratio limited condition
Low temperature and low load
|-
Force Mode
Force button was pressed on outdoor unit, forcing
100% compressor capacity
A
Oil return mode
Long compressor operation time
dF
Defrost mode
Outdoor coil freezes
Table 28
Fault code and system protection status table
** If the fi rst digit shown on the control board LED is one of the following Limited Condition Status codes
(followed by two numerical digits which show the current compressor frequency in Hz), the unit will continue
to run but in a limited condition. The only exception is when the system is in defrost mode, which only
displays "dF" (without any numerical digits following).