7 6 |
Bosch IDS 2.0
Service Manual
07.2021
|
Bosch Thermotechnology Corp.
Data subject to change
Component Check
Measure location
Parameter
When to check
High voltage power supply
Terminal Block
(L1-L)
172-270V(AC)
When there is high voltage power to unit
Low voltage power supply
CN9 Thermostat connection
(Y-C, B-C, W-C)
18-30V(AC)
When there is call from thermostat
LED Display
DSP1
CODE or numbers
When there is high voltage power to unit
DC motor control power
CN3
(+15V-N)
14-18V(DC)
When there is call from thermostat
DC voltage
CN3
(P-N)
370-385V(DC)
When compressor starts
LED light
LED 1/2/3
Light or fl ash
When there is call from thermostat
Reversing valve (RV)
CN12
Light or fl ash
When there is B call from thermostat
CCH - Crank Case Heater
CN8
24-36V(AC)
At initial power on/long period in standby mode,
see IOM
PEV - Pressure Equalization Valve
CN17
172-270V(AC)
At initial power on/start up sequence
EEV – Electronic Expansion Valve
CN13
(All pins-GND)
12V(DC)
When there is B call from thermostat
PT - Pressure transducer
CN16
(+5V-GND)
5V (DC)
When there is high voltage power to unit
HPS - High pressure switch
CN10
1Ω
When power OFF at breaker
Compressor
U-V, V-W, W-U
<1.5Ω (3T), <1Ω (5T)
When power OFF at breaker
Table 51
Outdoor Board Component Check