Modular fire panel
Planning | en
29
Bosch Sicherheitssysteme GmbH
System Information
07.2020 | 12.0 | F.01U.028.089
–
Limits per LSN 0300 module:
–
Up to 127 LSN classic elements or 254 LSN improved elements can be connected
–
Current consumption of up to 300 mA
–
Cable length of up to 1600 m
–
Limits per LSN 1500 module:
–
Up to 127 LSN classic elements or 254 LSN improved elements can be connected
–
Up to 1500 mA current consumption if LSN improved elements are connected
–
Up to 300 mA current consumption if LSN classic elements are connected
–
Cable length of up to 3000 m
–
As stipulated by EN 54‑2, panels with more than 512 LSN elements must be equipped
with a redundant panel controller.
Refer to
–
–
–
Achievable Cable Length with LSN 0300 A, page 36
3.2
Detection Points
Each element or input that can trigger an alarm counts as an detection point. One stand-alone
panel manages up to 4096 detection points. A panel operated in a network is limited to 2048
points.
All elements and inputs that do not use the Input type in the Message type setting are
regarded as detection points. Therefore, all elements and inputs for which one of the
following settings is programmed as the Message type are regarded as detection points:
–
Fire
–
Internal fire
–
Supervisory
–
Multi-criterion
–
Smoke
–
Fault
–
Heat
–
Water
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
Modules
Detection Points
CZM 0004 A
Up to 4 (1 detection point per zone)
IOP 0008 A
Up to 8 (1 detection point per monitored input)
RMH 0002 A
Up to 2
ENO 0000 B
requires 1 detection point only if a FSE release element is
connected and programmed using the FSP-5000-RPS
programming software
FPP‑5000‑TI
2
Interface Modules
Detection Points
FLM-420/4CON
Up to 2