150
en | Technical Data
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
Safety standards
EN 60950
Protection class
IP 30
Alternative technical data is listed for the individual modules.
7.5.1
ANI 0016 A Annunciator Module
Display elements
16 red LEDs, 16 yellow LEDs
Input voltage
20 V DC to 30 V DC
Maximum current consumption
–
Standby mode (all LEDs off)
6 mA
–
In case of alarm (all LEDs on)
26 mA
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
approx. 206 g
7.5.2
BCM‑0000‑B Battery Controller Module
Input voltage
20.4 V to 30 V
Current consumption at 23 V DC
–
Standby operation
25 mA
–
Fault
40 mA
Permissible battery capacities
–
with 2 batteries
24 to 26 Ah, 36 to 45 Ah
–
with 4 batteries
48 to 52 Ah, 72 to 90 Ah
Maximum current
–
of the module
Max. 6 A
–
to panel rails
Max. 6 A
–
for switch outputs
Max. 5.6 A (2 x 2.8 A cannot be connected in
parallel)
Maximum load of fault outputs BAT
FAULT, AC FAULT and collective fault
0 V/0 - 20 mA
Maximum battery resistance (fault
threshold)
430 mΩ
Voltage outputs
–
2 switchable outputs
+24 V (20.4 - 30 V), 2.8 A, battery buffered
(programmable)
Display and operating elements
–
1 green LED
Mains power on
–
3 yellow LEDs
Mains fault /fault in battery 1/fault in battery 2