Modular fire panel
Maintenance and Service | en
143
Bosch Sicherheitssysteme GmbH
System Information
07.2020 | 12.0 | F.01U.028.089
5.4.4
Testing the Addressing/Activation
1.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
triggering the corresponding assigned detector.
2.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
initiating the corresponding fault.
3.
Test the activation of extinguishing systems, door controls etc.
4.
Test all internal alarm signaling equipment (e.g. audible and visual notification
appliances).
6
Maintenance and Service
In Germany, maintenance work and inspection work on security systems are governed by the
regulations of DIN VDE 0833. These regulations stipulate reference to the manufacturer’s
instructions for maintenance intervals.
Notice!
Have maintenance and inspection work carried out regularly by trained, qualified personnel.
Bosch recommends a functional and visual inspection at least once a year.
Danger!
The fire panel and devices contain live components.
Touching live components can result in electric shock.
Disconnect the power supply before all maintenance or installation work.
6.1
Warranty
Defective devices are exchanged free of charge in the case of a claim under the warranty.
6.2
Repair
In the event of any defect, the entire device is exchanged.
6.3
Disposal
Unusable electrical and electronic devices must not be disposed of with
normal household waste. They must be disposed of in compliance with the
applicable regulations and directives (e.g. WEEE in Europe). See
www.boschsecurity.com/xc/en/weee/ for further information.
6.4
Additional Documentation
The installation instructions and operating instructions supplied with the device are available
as PDF files at www.boschsecurity.com.
Additional documents (including the Wiring guide) are available to those with access rights at
the extranet.
Notice!
The hexadecimal error codes can be found at the extranet (access rights required): LSN
diagnostic data (F.01U.081.090).