20
en | Technical data
Conventional aspiration smoke detector
2020.04 | 3 | F.01U.130.927
Quick installation guide
Bosch Sicherheitssysteme GmbH
Max. current consumption (at 24 V)
FCS-320‑TP1
FCS-320-TT1
FCS-320‑TP2
FCS-320‑TT2
–
Starting current, fan voltage 6.9 V (without reset
board)
300/300 mA
320/330 mA
–
Starting current, fan voltage 9 V (without reset
board)
300/300 mA
320/330 mA
–
On standby, fan voltage 6.9 V (without reset
board)
200/200 mA
220/230 mA
–
On standby, fan voltage 9 V (without reset board) 275/260 mA
295/310 mA
–
On alarm, fan voltage 6.9 V (without reset board) 210/230 mA
240/290 mA
–
On alarm, fan voltage 9 V (without reset board)
285/290 mA
315/370 mA
Reset board current consumption
Max. 20 mA
Mechanics
Displays on the device FCS-320-TP1/FCS-320-TP2
–
Operation
Green LED
–
Fault
Yellow LED
–
Alarm
1 red LED/2 red LEDs
Displays on the device FCS-320-TT1/FCS-320-TT2
–
Operation
Green LED
–
Fault
Yellow LEDs
–
Level display
1 x / 2 x smoke level display, each
with 10 segments (1-10)
–
Alarm
1 x 3 / 2 x 3 red LEDs for info alarm,
internal alarm and main alarm
Conical duct connections for Ø 25 mm
–
Aspiration pipe
1 pipe/2 pipes
–
Air-return pipe
1 pipe
Cable bushings
5 x M 20 and 2 x M 25
Dimensions (H x W x D)
292 x 200 x 113 mm
Weight
Approx. 1.5 kg
Housing material
Plastic (ABS)
Housing color
Papyrus white (RAL 9018)
Environmental conditions
Protection category as per EN 60529
IP 20
Permissible temperature range