14
en | System overview
Conventional aspiration smoke detector
2020.04 | 3 | F.01U.130.927
Quick installation guide
Bosch Sicherheitssysteme GmbH
1
System overview
For FCS-320‑TP1 and FCS-320‑TP2 connections, refer to graphic
01, page 4
.
Position in
figure
Function
Explanation
FCS-320 series
1
Cable bushing for connection of fire panel
and additional power supply (input/
output)
1 x M 20, for cable diameters of
8 - 12 mm
2
Pipe system 1 connection
For Ø 25 mm pipe system
3
Pipe system 2 connection (only for devices
with a two pipe system)
For Ø 25 mm pipe system
4
Connection for air-return pipe
5
Cable bushing for connection of fire panel
and additional power supply (input/
output)
2 x M 25 for cable diameters of
9 - 14 mm (expandable to 14 -
18 mm)
For FCS-320‑TP1 and FCS-320‑TP2 LEDs, refer to graphic
FCS-320-TP
Designation
LED
Color
Explanation
I
Operation
Green
Operation
II
Alarm
1
Red
Alarm
III
Fault
Yellow
Fault
–
in the pipe system
–
of a detector module
–
caused by fan failure
1
Two alarm LEDs on the FCS-320-TP2
For jumper assignment, refer to graphic
JU1 Pin 1+2 Fan voltage
6.9V
Bypassed
9V
Open
Collective fault contact detector module 1
JU2 Pin 1+2
JU2 Pin 2+3
NC
Bypassed
NC
Open
NO
Open
NO
Bypassed
Collective fault contact detector module 2
JU3 Pin 1+2
JU3 Pin 2+3
NC
Bypassed
NC
Open
NO
Open
NO
Bypassed
JU4 Pin 1+2 Number detector modules
6.9V
Bypassed