background image

DX2010 Installation Instructions

© 2004 Bosch Security Systems

Page 3

If the DX2010 Module is powered by an external
12 VDC power supply, the output terminals can
supply power for up to 450 ft. (138 m) from the
DX2010 to the remotely powered devices.

If the DX2010's Aux Output ("+Out-" terminals) is
used as an auxiliary power source, the DX2010's R
and B wires must be home-run to either the panel
or to an auxiliary power supply. Do not use a daisy-
chain wire configuration (see Figure 6
).

TMPR

G

Y

1 COM

+OUT-

(-)

(+)

Motion Detectors,
Photobeams, etc.

Panel or
Auxiliary

Power Supply

R

B

Figure 6:  Auxiliary Output Connections

4.3 Tamper Input Connections

Each DX2010 provides an input for tamper devices. The tamper
input monitors external Normally Closed (NC) tamper switches
when wired as shown in Figure 7. The tamper circuit must be
closed to provide proper DX2010 tamper supervision to the control
panel. Do not use an EOL resistor.

The DX2010 also provides an on-board tamper switch for use if
the DX2010 is installed inside the AE20 plastic enclosure. The
cover tamper spring is supplied with the DX2010. The on-board
tamper switch cannot be used if the DX2010 is mounted inside the
control panel’s enclosure (wire the tamper input as shown in
Figure 7 if installed in the control panel’s enclosure).

Use either the tamper input or the on-board tamper switch. Both
cannot be used simultaneously.

1

R

B

G

Y

DX2010

+OUT-

TMPR

COM

On-board

tamper switch

Figure 7:  Tamper Wiring

If neither the tamper input nor the on-board tamper switch are
used, a wire jumper must be placed as shown in Figure 8.

1

R

B

G

Y

DX2010

+OUT-

TMPR

COM

On-board

tamper switch

Figure 8:  Wire Jumper Location

4.4 Sensor Loop Connections

The DX2010 has the capacity for both Normally Open (N/O) and
Normally Closed (N/C) contacts. Wire the inputs as shown in
Figure 9.

The DX2010 is not designed for use with two-wire
smoke detectors.

Only use Normally Open (N/O) contacts for fire
applications.

1

2

3

4

5

6

7

8

COM

COM

COM

COM

Use 2.21 K EOL

Figure 9:  Single Point/Zone Sensor Loop Wiring

For Point/Zone Doubling, wire the inputs as shown in Figure 10.

Each loop is monitored

as a separate point.

Open for alarm
otherwise
Normally Closed

Open for alarm
otherwise
Normally Closed

2.2 k 

3.65 k 

Input

Terminals

1 to 8

Common

DX2010 Inputs

9-16

DX2010 Inputs

1-8

Figure 10:  Doubled Point/Zone Wiring

Zone doubling is not permitted for fire applications.

Содержание DX2010

Страница 1: ...with appropriate EOL resistor s for supervision Control Panel Compatibility DS7240 DS7220 D6412 D4412 3 0 Mounting Failure to follow the instructions in this manual may result in personal injury and or damage to the equipment The DX2010 contains static sensitive components and must be handled with care Follow anti static procedures when handling the modules Test according to NFPA72 if used in fire...

Страница 2: ...a Y Figure 5 External Power Supply Connections See Table 1 for the data bus wiring length requirements 22 AWG 0 8 mm 18 AWG 1 2 mm Panel to DX2010 DX2010 AUX Output not used 1000 ft 305 m 2000 ft 610 m Panel to DX2010 DS2010 AUX Output supplying 100 mA 100 ft 30 m 250 ft 76 m Table 1 Wire Lengths Wire length may be restricted by panel limitations See the panel s Installation Guide for more informa...

Страница 3: ... board tamper switch cannot be used if the DX2010 is mounted inside the control panel s enclosure wire the tamper input as shown in Figure 7 if installed in the control panel s enclosure Use either the tamper input or the on board tamper switch Both cannot be used simultaneously 1 R B G Y DX2010 OUT TMPR COM On board tamper switch Figure 7 Tamper Wiring If neither the tamper input nor the on board...

Страница 4: ...switches cycle the power to the DX2010 turn the power off and then on for the address change to take effect L COM L 2 2 k EOL Resistor 2 2 k EOL Resistor 1 5 k or 2 2 k Alarm Resistor 1 5 k or 2 2 k Alarm Resistor Alarm Contacts Tamper Contacts Tamper Contacts Figure 11 Dual Point Zone Input Wiring ON 1 2 3 4 5 6 Status LED Figure 12 DX2010 Status LED ON 1 2 3 4 5 6 OFF ON Example Module Address 1...

Отзывы: