background image

© 2004 Bosch Security Systems
130 Perinton Parkway, Fairport, New York, USA 14450-9199
Customer Service: (800) 289-0096; Technical Support: (888) 886-6189

03/04

DX2010 Installation Instructions

P/N: 49533E     Page 4

4.5 Tamper Point/Zone Inputs

This feature is not available for some control/communicators.
Consult your control/communicator’s Installation Instructions.

The DX2010 has the capacity for dual tamper point/zone inputs
utilizing two EOL resistors (using 1.5k or 2.2k Alarm Resistor). See
Figure 11.

5.0

DX2010 LED Operation

The DX2010 LED  (Figure 12) flashes to indicate the status of the
device. The LED indications are:

• One flash per second indicates normal operation.

• LED steady ON can indicate any of the following:

- G wire is not connected or there is a communications problem

between the control panel and the DX2010.

- No locations/points are assigned to the DX2010 with this

address. See your control/communicator’s programming
guide for location/point assignment instructions.

- Address on the DX2010 is not set correctly.

• LED OFF indicates that there is no power to the module.

6.0

Setting the DX2010’s Address

Use Table 2 to configure the DX2010’s address. Refer to the control/
communicator’s installation manual to determine the appropriate
address for each DX2010 you connect. Figure 13 shows the DIP
switch configuration.

Each time you change the address DIP switches,
cycle the power to the DX2010 (turn the power off
and then on) for the address change to take effect.

L+

COM

L+

2.2 k

EOL

Resistor

2.2 k

EOL

Resistor

1.5 k or 2.2 k

Alarm

Resistor

1.5 k or 2.2 k

Alarm

Resistor

Alarm

Contacts

Tamper

Contacts

Tamper

Contacts

Figure 11:  Dual Point/Zone Input Wiring

ON

1

2

3

4

5

6

Status LED

Figure 12:  DX2010 Status LED

ON

1

2

3

4

5

6

OFF

ON

Example:

Module Address 102

Figure 13:  DIP Switch Configuration

 

DIP Switch Settings 

 

DIP Switch Settings 

DIP 

Switches 

S1 

S2 

S3 

S4 

S5 

S6 

DIP 

Switches 

S1 

S2 

S3 

S4 

S5 

S6 

Module 

Address 

32 

16 

Module 

Address 

32 

16 

101 

OFF OFF OFF OFF OFF OFF 

117 

OFF  ON 

OFF OFF OFF OFF 

102 OFF 

OFF 

OFF 

OFF 

OFF 

ON 

118 OFF 

ON 

OFF OFF OFF  ON 

103 OFF 

OFF 

OFF 

OFF 

ON 

OFF 119 OFF 

ON 

OFF OFF  ON 

OFF 

104 OFF 

OFF 

OFF 

OFF 

ON ON  120 OFF 

ON 

OFF OFF  ON ON 

105 OFF 

OFF 

OFF 

ON 

OFF OFF 

121 

OFF  ON 

OFF 

ON 

OFF OFF 

106 OFF 

OFF 

OFF 

ON 

OFF 

ON 

122 OFF 

ON 

OFF 

ON 

OFF 

ON 

107 OFF 

OFF 

OFF 

ON ON OFF 123 OFF 

ON 

OFF 

ON ON OFF 

108 OFF 

OFF 

OFF 

ON ON ON  124 OFF 

ON 

OFF 

ON ON ON 

109 OFF 

OFF 

ON 

OFF OFF OFF 

125 

OFF  ON ON OFF OFF OFF 

110 OFF 

OFF 

ON 

OFF OFF  ON 

126 OFF 

ON ON OFF OFF  ON 

111 OFF 

OFF 

ON 

OFF 

ON 

OFF 127 OFF 

ON ON OFF 

ON 

OFF 

112 OFF 

OFF 

ON 

OFF 

ON ON  128 OFF 

ON ON OFF 

ON ON 

113 OFF 

OFF 

ON ON OFF OFF 

129 

OFF  ON ON ON OFF OFF 

114 OFF 

OFF 

ON ON OFF 

ON 

130 OFF 

ON ON ON OFF 

ON 

115 OFF 

OFF 

ON ON ON OFF 131 OFF 

ON ON ON ON OFF 

116 OFF 

OFF 

ON ON ON ON  132 OFF 

ON ON ON ON ON 

ON indicates the DIP switch is in the ON position; OFF indicates the DIP switch is in the OFF position. 

Table 2:  Address Jumper Settings

Содержание DX2010

Страница 1: ...with appropriate EOL resistor s for supervision Control Panel Compatibility DS7240 DS7220 D6412 D4412 3 0 Mounting Failure to follow the instructions in this manual may result in personal injury and or damage to the equipment The DX2010 contains static sensitive components and must be handled with care Follow anti static procedures when handling the modules Test according to NFPA72 if used in fire...

Страница 2: ...a Y Figure 5 External Power Supply Connections See Table 1 for the data bus wiring length requirements 22 AWG 0 8 mm 18 AWG 1 2 mm Panel to DX2010 DX2010 AUX Output not used 1000 ft 305 m 2000 ft 610 m Panel to DX2010 DS2010 AUX Output supplying 100 mA 100 ft 30 m 250 ft 76 m Table 1 Wire Lengths Wire length may be restricted by panel limitations See the panel s Installation Guide for more informa...

Страница 3: ... board tamper switch cannot be used if the DX2010 is mounted inside the control panel s enclosure wire the tamper input as shown in Figure 7 if installed in the control panel s enclosure Use either the tamper input or the on board tamper switch Both cannot be used simultaneously 1 R B G Y DX2010 OUT TMPR COM On board tamper switch Figure 7 Tamper Wiring If neither the tamper input nor the on board...

Страница 4: ...switches cycle the power to the DX2010 turn the power off and then on for the address change to take effect L COM L 2 2 k EOL Resistor 2 2 k EOL Resistor 1 5 k or 2 2 k Alarm Resistor 1 5 k or 2 2 k Alarm Resistor Alarm Contacts Tamper Contacts Tamper Contacts Figure 11 Dual Point Zone Input Wiring ON 1 2 3 4 5 6 Status LED Figure 12 DX2010 Status LED ON 1 2 3 4 5 6 OFF ON Example Module Address 1...

Отзывы: