Page 2

© 2004 Bosch Security Systems

DX2010 Installation Instructions

Another mounting option for the DX2010 is a D203 Enclosure. See
Figure 3.

Install the module
in the D20 Enclosure.

Figure 3:  Mounting the DX2010 in a D203 Enclosure

4.0

Wiring

Remove all power to the system (AC and standby
battery) before making or breaking any
connections. Failure to do so might result in
personal injury and/or damage to the equipment.

4.1 Data Bus Connections

Connect the DX2010 to the control/communicator data and auxiliary
power sources. The DX2010 can be powered directly from the
data bus (see Figure 4).

+OUT-

TMPR

1 COM

R

B

G

Y

Red (+)

Black (-)

Green (Data)

Yellow (Data)

To

Control/Communicator

Data Bus

DX2010

Figure 4:  Control/Communicator Connections

If using an external 12 VDC power supply, wire as shown in
Figure 5.

When using any external power supply, the negative
(-) output must not be tied to earth ground. A ground
fault condition will be reported if negative (-) is
grounded.

+OUT-

TMPR

1 COM

R

B

Red (+)

To

Control/Communicator

Data Bus

DX2010

External 12 VDC

Power Supply

(+)

(-)

Black (-)

G

Green (Data)

Yellow (Data)

Y

Figure 5:  External Power Supply Connections

See  Table 1 for the data bus wiring length requirements.

 

#22 AWG 

(0.8 mm) 

#18 AWG 

(1.2 mm) 

Panel to DX2010 
DX2010 AUX Output not used 

1000 ft. 

(305 m)

*

 

2000 ft. 

(610 m)

*

 

Panel to DX2010 
DS2010 AUX Output supplying 
100 mA 

100 ft. 

(30 m)

**

 

250 ft. 

(76 m)

**

 

Table 1:  Wire Lengths

* Wire length may be restricted by panel limitations. See the panel’s

Installation Guide for more information.

** If the DX2010 is powered directly by an external auxiliary power

supply (Figure 5), use the wire lengths specified in the first row
of Table 1.

4.2 Auxiliary Output Connections

The DX2010 has the capacity to provide 12 VDC at up to 100 mA
from the Auxiliary Output (+) OUT (-) terminals to power external
devices such as motion detectors (see Figure 6).

If a trouble condition occurs on the DX2010 (such as an overcurrent
condition), it  sends a data bus trouble message to the panel.

When using the auxiliary output on the DX2010, the
maximum distance between the control/
communicator and the module must be limited to
250 ft. (76 m) using #18 AWG (1.2 mm) wire or
100 ft. (30 m) using #22 AWG (0.8 mm) wire. The
maximum distance from the DX2010 output
terminals and the external devices (PIRs, smoke
detectors, etc.) must be limited to 50 ft. (15 m) for
#22 AWG (0.8 mm) or 100 ft. (30 m) for #18 AWG
(1.2 mm) wire.

Содержание DX2010

Страница 1: ...with appropriate EOL resistor s for supervision Control Panel Compatibility DS7240 DS7220 D6412 D4412 3 0 Mounting Failure to follow the instructions in this manual may result in personal injury and or damage to the equipment The DX2010 contains static sensitive components and must be handled with care Follow anti static procedures when handling the modules Test according to NFPA72 if used in fire...

Страница 2: ...a Y Figure 5 External Power Supply Connections See Table 1 for the data bus wiring length requirements 22 AWG 0 8 mm 18 AWG 1 2 mm Panel to DX2010 DX2010 AUX Output not used 1000 ft 305 m 2000 ft 610 m Panel to DX2010 DS2010 AUX Output supplying 100 mA 100 ft 30 m 250 ft 76 m Table 1 Wire Lengths Wire length may be restricted by panel limitations See the panel s Installation Guide for more informa...

Страница 3: ... board tamper switch cannot be used if the DX2010 is mounted inside the control panel s enclosure wire the tamper input as shown in Figure 7 if installed in the control panel s enclosure Use either the tamper input or the on board tamper switch Both cannot be used simultaneously 1 R B G Y DX2010 OUT TMPR COM On board tamper switch Figure 7 Tamper Wiring If neither the tamper input nor the on board...

Страница 4: ...switches cycle the power to the DX2010 turn the power off and then on for the address change to take effect L COM L 2 2 k EOL Resistor 2 2 k EOL Resistor 1 5 k or 2 2 k Alarm Resistor 1 5 k or 2 2 k Alarm Resistor Alarm Contacts Tamper Contacts Tamper Contacts Figure 11 Dual Point Zone Input Wiring ON 1 2 3 4 5 6 Status LED Figure 12 DX2010 Status LED ON 1 2 3 4 5 6 OFF ON Example Module Address 1...

Отзывы: