28
en | Technical data
Radio Frequency Fire Detection System
2016.04 | 6.0 | 4.998.120.885
Operation Guide
Bosch Sicherheitssysteme GmbH
10
Technical data
FK 100 LSN RF Interface Module
LSN input voltage
10 to 33 V DC
AUX input voltage
20 to 30 V DC
Current consumption
–
LSN
–
AUX
7 mA
< 20 mA
Frequency range
868 to 870 MHz (SRD band)
Channel spacing
25 kHz
Maximum number of RF interface modules
10 per LSN loop
Max. number of RF smoke detectors
30 DOW 1171 per FK 100 LSN
Maximum number of RF manual call points
10 SMF121 per FK 100 LSN
Protection category
IP 30
Permissible ambient temperature
-10 °C to +55 °C
Housing material
Plastic, ABS Terluran
Housing color
light-gray, RAL 9002
Dimensions (H x W x D)
135 x 100 x 35.7 mm
Weight
Approx. 200 g
DOW 1171 RF Smoke Detector
Power supply
2 x 9 V lithium batteries
Battery service life
approx. 5 years
Average current consumption
0.07 mA
Frequency range
868 to 870 MHz (SRD band)
Channel spacing
25 kHz
Maximum transmitting power
5 mW
Maximum range in buildings
(Depending on environment)
40 m
Detection principle
Scattered-light measurement
Protection category (as per EN 60 529)
IP 44
Permissible ambient temperature
-10 °C to +55 °C
Maximum relative humidity
95% at T < 34 °C
Housing material
Plastic, PC/ABS
Housing color
white, similar to RAL 9010
Dimensions (D x H)
119 x 73 mm
Weight
approx. 335 g