Installing the RF Fire Detection System | en
17
Bosch Sicherheitssysteme GmbH
Operation Guide
2016.04 | 6.0 | 4.998.120.885
5.3
Installing the SMF121 RF Manual Call Point
Notice!
Do not connect the batteries in the RF manual call point until the RF interface module is
permanently connected to the power supply. If this is not the case, the detector constantly
tries to establish a connection to the RF interface module, which substantially reduces the
service life of the batteries.
96
96
35
9
9
1
116,3
11
6,
3
1360 ± 200
2
Figure 5.13: SMF6120 Detector Base Dimensions
1
Space to open the door
2
Mounting height
The RF manual call point is suitable for surface-mounting on a wall. Select the installation
location so that approx. 35 mm is left free to the right (1) to open the door, and so that the
detector is easily accessible for service and maintenance work.
The mounting height (2) from the ground to the center of the push button, in line with VdS
regulation, amounts to 1400 mm (± 200 mm).
1.
First install the SMF6120 Detector Base.
2.
Then wire up the SMF6120 Base to the SMF121 RF Manual Call Point in line with chapter
Connection of SMF121 RF Manual Call Point to SMF6120 Base, page 19
.
3.
Then install the SMF121 RF Manual Call Point on the base.