en | Commissioning a RF Fire Detection System
Radio Frequency Fire Detection System
2016.04 | 6.0 | 4.998.120.885
Operation Guide
Bosch Sicherheitssysteme GmbH
Flash rate per second
Field strength Meaning
4 times
High
Secure transfer
=> Detector is positioned correctly
3 times
Average
Twice
Low
Insecure transfer
=> Detector must be repositioned
Once
Very low
Notice!
Logging in is only successful if the field strength is high or average, or a secure transfer is
guaranteed.
As soon as all the RF detectors have been logged in, the RF interface module automatically
starts the system configuration and the green LED on the RF interface module flashes slowly.
After a successful system configuration, the green LED stays continuously lit. If the interface
module housing is open, the yellow LED is also lit.
The system is then automatically re-initialized by the fire panel and switches over to standard
mode.
7.2.2
Logging in the SMF121 RF Manual Call Points to the RF Interface Module
Notice!
In some cases, it may be that a RF manual control point, which was already in operation,
forgets that it was logged in. In this case, follow the instructions as for a new detector.
1.
Trigger the manual call point by pressing the push button.
2.
Connect the batteries in the detector base.
The green LED on the right of the PC board flashes briefly once per second.
If the green LED flashes three times every 2 seconds, the detector must be reset to the
delivery state. To do this, press the
new
button at the bottom left of the PC board in the
detector base until the green LED has changed from flashing 3 times every 2 seconds to
flashing once per second.
3.
Press the reset lever to the left to reset the push button.
The green LED to the right of the PC board changes from briefly flashing once to flashing
slowly once every 2 seconds, and the detector starts logging in.
4.
Now log in all the detectors one after the other. In so doing, take note of the sequence
entered in the WinPara / FSP-5000-RPS configuration.
Once the detector has been logged into the interface module, the green LED on the detector's
PC board goes out and then starts flashing again for approx. 2 minutes. The flash rate shows
the field strength (quality of the radio connection).
Flash rate per second
Field strength Meaning
4 times
High
Secure transfer
=> Detector is positioned correctly
3 times
Average
Twice
Low
Insecure transfer
=> Detector must be repositioned
Once
Very low