Radio Frequency Fire Detection System
Commissioning a RF Fire Detection System | en
23
Bosch Sicherheitssysteme GmbH
Operation Guide
2016.04 | 6.0 | 4.998.120.885
Notice!
Logging in is only successful if the field strength is high or average, or a secure transfer is
guaranteed.
As soon as all the RF detectors have been logged in, the RF interface module automatically
starts the system configuration and the green LED on the RF interface module flashes slowly.
After a successful system configuration, the green LED stays continuously lit. If the interface
module housing is open, the yellow LED is also lit.
The system is then automatically re-initialized by the fire panel and switches over to standard
mode.
7.3
Manually Operating the FK 100 LSN RF Interface Module
Notice!
If you operate the RF interface module without the fire panel and WinPara / FSP-5000-RPS, a
permanent power supply to the RF interface module must be guaranteed.
1.
Insert the wired terminal block for the power supply into the RF interface module (wiring
see chapter
Connection of FK 100 LSN RF Interface Module to the Fire Panel, page 18
).
The red LED on the RF interface module lights up for approx. 10 seconds. Then the yellow
LED flashes slowly.
2.
Activate the reed contact in the RF interface module, by moving a magnet along the left
side of the interface module housing (see the order information in chapter
Order
information, page 27
).
The red LED on the RF interface module lights up for approx. 10 seconds. As soon as it
goes out, the green and yellow LEDs start to flash rapidly and the automatic search for a
base channel (frequency) starts. After a successful search (approx. 1 to 5 minutes), the
yellow LED goes out.
3.
Now log in all the RF detectors one after the other to the RF interface module as
described in chapter
Commissioning DOW 1171 and SMF121 RF Detectors, page 21
.
4.
After all the RF detectors have been logged in, and the flashing to display the field
strength has gone out on the last detector, activate the reed contact in the RF interface
module again, by moving a magnet along the left side of the interface module housing.
The RF interface module automatically starts the system configuration, while the green
LED on the RF interface module flashes slowly. After a successful system configuration,
the green LED stays continuously lit.