24
en | Power Supply and Power Outputs
2016.07 | 04 | F.01U.291.483
UL Installation Guide
Bosch Security Systens, Inc.
!
Warning!
High current arcs are possible. The positive (red) battery lead and Terminal 5 can create high
current arcs if shorted to other terminals or the enclosure. Use caution when working with
the positive lead and Terminal 5. Always disconnect the positive (red) lead from the battery
before removing it from Terminal 5.
!
Warning!
The battery terminals and wire are not power limited. A 0.250 in (6.4 mm) space must be
maintained between the battery terminals, battery wiring, and all other wiring. Battery wiring
cannot share the same conduit, conduit fittings, or conduit knock-outs with other wiring.
Refer to the Battery Terminals illustration.
Figure 4.13: Battery Terminals
Callout - Description
1 - Battery terminals. Terminal 5 is non-power limiting.