30
en | Specifications
2016.07 | 04 | F.01U.291.483
UL Installation Guide
Bosch Security Systens, Inc.
SDI Bus
SDI Bus A+:
9 VDC 15000 ft (4572 m) maximum
SDI Bus B-:
9 VDC 15000 ft (4572 m) maximum
SDI2 Bus
SDI2 Bus A+; 12 VDC nominal 7500 ft (2286 m) maximum
3
SDI2 Bus B-:
12 VDC nominal 7500 ft (2286 m) maximum
3
Telephone
Connections
Connection:
RJ31X or RJ38X jack can connect the control panels.
Two telco
lines:
Bosch Security Systems, Inc. D928 Dual Phone Line
Module required for two phone line service. Supervision
supplied by the control panel.
3
See SDI2 Bus Wiring Recommendations for more details
Battery
Discharge/
Recharge
Schedule
Discharge
Cycle:
13.9 VDC
Charging float level.
13.8 VDC
Charging status LED on.
12.1 VDC
Low Battery Reports if programmed. Low
Battery LED on.
10.2 VDC
Minimum operational voltage.
10.0 VDC
Battery load shed.
Recharge
Cycle:
AC ON
Load shed relay resets, battery charging
begins, Battery Trouble and AC Restoral
Reports sent.
13.7 VDC
Battery Restoral Report sent, Low Battery
LED off.
13.9 VDC
Charging status LED off, battery float
charged.
Environmental
Temperature: +32
゚
F to +120
゚
F (0
゚
C to +49
゚
C)
Relative
Humidity:
Maximum 93% non-condensing
Arming Stations
B915/B920/B930/B921C/B942 Keypads, D1255/D1255B/D1255RB
Keypads, D1256RB Fire Command Centers; D1257RB Fire Alarm
Annunciators; D1260/D1260B Keypads; D1265 Keypads; Keyswitch;
Keyfobs
Point
Thresholds
On-board
Points 1 to 8
Open
Greater than 3.7 VDC, but less than 5.0
VDC.
Normal
Greater than 2.0 VDC, but less than 3.0
VDC
Short
Greater than 0.0 VDC, but less than 1.3
VDC.
Compatible
Enclosures
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack
Resistant Enclosure, BATB-40/BATB-80 Battery Box
2
See SDI2 Bus Wiring Recommendations for more details