background image

 D7212GV2 

 

 

  D7212GV2 Release Notes for Version 7.07   

 

© 2007 Bosch Security Systems, Inc. 

Page 7 

F01U009079-04 

Idle Text Scroll Lock 

To comply with UL requirements for a Fire 
Command Center, set the idle text scroll lock feature 
to 

Yes

. Select 

GV2MAIN

COMMAND 

CENTER

Command Center Assignments

 

CC# Idle Scroll Lock

. The D125xRB keypad idle 

text display locks until a user manually acknowledges 
an alarm or trouble condition. The unacknowledged 
idle text display updates automatically to the highest 
priority alarm or trouble type if one occurs. When the 
user presses the [NEXT] key, the idle display is 
acknowledged and the scroll is unlocked.  

Auxiliary Power Supply Monitor 

A new point type is added to monitor auxiliary power 
supply modules. If 

P# Point Type

 is programmed 

with 

11 – Aux AC Supervision

 and the associated 

point goes off-normal, a Point Trouble condition 
occurs immediately. Any Trouble events generated 
from an Aux AC Supervision point are delayed by the 
time programmed in 

AC Fail Time

.  

Battery Recharge Circuit Monitor 

Control panel firmware now monitors the battery 
recharge circuit to ensure that the backup power of 
the control panel is available when needed. If the 
control panel detects that the on-board battery is not 
recharging correctly because of a hardware failure, a 
battery trouble condition occurs. This feature is always 
on and cannot be disabled. 

Reset Switch Trouble Annunciation 

A new feature is added to annunciate trouble locally if 
the Reset Switch (S1) is closed. The trouble 
annunciation is an intermittent beep from the on-
board sounder. The sounder is silenced when the 
switch is opened. This feature is always on and cannot 
be disabled. 

Fire Bypass Trouble Annunciation 

The Fire Bypass warning display is modified to 
generate a Trouble warning tone that can be silenced 
with [COMMAND[[4]. The trouble condition self-
clears when all bypassed fire points within the 
keypad’s scope return to service. This feature is always 
on and cannot be disabled. 

Summary Fire Relay Options 

An option is added that changes the duration of the 
Panel Wide Summary Fire Relay output. Select 

GV2AUX

MISCELLANEOUS

Fire Summary 

Sustain

Yes

  Summary Fire Relay clears when all Fire 

Alarms are cleared from the display. 

No 

Summary Fire Relay

 

clears when the area 

Fire Alarms are silenced and all area Fire 
Points return to normal. 

The default option is 

No

. This option is consistent 

with the Summary Fire Relay operation in the 
previous versions of the D7212G Control Panel. This 
feature provides a way to maintain the fire strobes 
after the alarm bell outputs are silenced. 

Enhanced Communication Trouble 

 

The default configuration parameters for 
the poll rate, ACK wait time, and number 
of retries complies with UL. 

When an Enhanced Communication Trouble 
condition occurs, it generates a system-wide trouble 
message (

COMM TRBL SDI ##

). The new trouble 

message includes the address of the virtual SDI 
device.  

 

Address 88 = Enhanced SDI Path 1 
Address 89 = Enhanced SDI Path 2 
Address 90 = Enhanced SDI Path 3 
Address 91 = Enhanced SDI Path 4 

The trouble condition is also sent through a backup 
path to the central station as 

Communication 

Trouble SDI ##

, using the same virtual address 

numbers as the trouble messages. The communication 
trouble event also creates new Modem IIIa

2

 messages 

that the central station might need to add to their 
automation software.  Refer to Events 157 to 160 in 
the 

Modem IIIa

2

 Messages

 section of the 

Appendix

 in the 

D6600 Computer Interface Manual

 (P/N: 4998122703) 

for the details of central station data changes.  

Содержание D7212GV2

Страница 1: ...07 RADXSKED v1 03 GV2AUX v1 01 Table 2 Supporting Literature for D7212GV2 with Version 7 07 Firmware and Later Document Name Part Number D7212GV2 Program Entry Guide F01U003804 03 D7212GV2 Program Record Sheet F01U003803 03 D7212GV2 Operation and Installation Guide F01U003805 02 D7212GV2 Approved Applications Compliance Guide F01U003806 02 Older revisions have alphabetic revision identifiers for e...

Страница 2: ...nt corrupted data account codes for systems that communicate with BIS 2 0 Security Engine These changes are only compatible with BIS Security Engine v2 1 1271 or later This addresses the issues described in the BIS SEE and GV2 G Series Technical Service Note P N F01U073249 Changes made allow the Relay Latches on point fault option for the P Relay Response Type feature to reset when a passcode is e...

Страница 3: ... is installed on the RPS workstation special software firewall settings might be required to allow outgoing traffic Refer to your firewall software for configuration information Any DX4020 or D9133TTL E used for enhanced communication to a central station receiver or with RPS over a network must be configured to use Datagram Mode 2 when the control panel firmware is version 7 06 and later Refer to...

Страница 4: ...evice are now included when a test report is sent using COMMAND 41 or a sked Corrections enhance the reliability and performance of RPS network connection These corrections also decrease the delay in reporting a break in the Ethernet connection to the control panel s Network Interface Module within the time limits required by UL For UL 1610 Line Security formerly Grade AA Intrusion System installa...

Страница 5: ... panel wide Communications Failure Relay output to activate when events in Route Groups 2 through 4 do not reach the central station Previously this relay output activated only on a communication failure for Route Group 1 2 5 Version 7 02 The Phone Line Supervision feature has improved accuracy in detecting the phone line The Modem IIIa2 product ID is changed to the same ID as the G Series control...

Страница 6: ...ion This feature was updated to manage the control panel clock adjustments over a period of time instead of simply jumping to the new time This enhancement allows consistent execution of Skeds at their intended times When a TimeSync adjustment is in process the Time Date idle text display is modified with a or sign to indicate control panel time is increasing or decreasing to match the target time...

Страница 7: ...ed Fire Bypass Trouble Annunciation The Fire Bypass warning display is modified to generate a Trouble warning tone that can be silenced with COMMAND 4 The trouble condition self clears when all bypassed fire points within the keypad s scope return to service This feature is always on and cannot be disabled Summary Fire Relay Options An option is added that changes the duration of the Panel Wide Su...

Страница 8: ...s the Entry Delay starts If the system is not disarmed within the programmed time an Exit Error Alarm is generated This feature is always enabled and has no configuration parameters The alarm with an exit error event creates a new Modem IIIa2 message that the central station might need to add to their automation software Refer to Event 38 in the Modem IIIa2 Messages section of the Appendix in the ...

Страница 9: ... after event transmission displays CANCEL RPT SENT on the keypad The burglary alarm cancel window duration is the time programmed in the A Alarm Bell prompt Duress Passcode Prompts Duress Type A Duress Enable L Send Duress A new duress option is available that allows any passcode with the L Send Duress permission set to Yes to always send a Duress Alarm event upon entry This feature allows the con...

Страница 10: ...nd simplifies system operation Passcode Controlled Menus The system prompts a user to enter a passcode before viewing the keypad function list menu The system shows the user the menu options allowed according to the user s authority level Passcode controlled menus simplify system operation by providing a user with unique and pertinent options and information This feature is not intended for use on...

Страница 11: ...lable The default values for the Bright Dim mode are Bright 10 and Dim 3 On the D1260 and D1260B Keypads when the Sensor Reset command COMMAND 47 is executed Call for Service appears erroneously for a brief time on the display This effect also occurs when the control panel reboots Change the Service Passcode User ID 0 factory default value when the ANSI SIA CP 01 required Passcode Length parameter...

Страница 12: ...ccount are armed the keypads in those areas display the text programmed in the Area Acct Is On prompt The control panel is supposed to provide a way to alternately use the display text programmed in the Area is On prompt under the same conditions but this feature is not yet available When an invisible point is programmed with P RlyResp Type set to 2 Relay Latches the relay must be manually reset u...

Отзывы: