Release Notes for Version 7.07
12/07
D7212GV2
Page 12 of 12
•
With a v7.06 or earlier D7212GV2 control panel,
if a network interface module (NIM) is
programmed as a Primary Device in any Route
Group, follow these programming rules:
-
Assign Enhanced Communication Path 1 as
the Primary Device in Route Group 1.
-
Assign Enhanced Communication Path 2 as
the Primary Device in Route Group 2.
-
Assign Enhanced Communication Path 3 as
the Primary Device in Route Group 3.
-
Assign Enhanced Communication Path 4 as
the Primary Device in Route Group 4.
•
When all areas associated with an account are
armed, the keypads in those areas display the text
programmed in the
Area # Acct Is On
prompt.
The control panel is supposed to provide a way to
alternately use the display text programmed in the
Area # is On
prompt under the same conditions,
but this feature is not yet available.
•
When an invisible point is programmed with
P# RlyResp Type
set to
2
(Relay Latches), the
relay must be manually reset using keypad
[COMMAND 54]. Only visible points allow their
associated relay to reset when the alarm memory
is cleared with this setting.
•
When the control panel is upgraded from V7.06
and earlier to V7.07 and later, the
AC Fail
Display
prompt defaults to 150 sec instead of to
the intended factory default of 60 sec.
•
The
Easy Exit
feature was disabled in firmware
version 7.07 to address
the issues described in
the
GV2 Arming Without Passcode Technical Service
Note
(P/N: F01U077005).