Appendix A: Approved Applications Compliance Guide
Appendix A: Approved Applications Compliance Guide
A-1
Listings and Approvals
Fire
• UL
• CSFM
• NYC-MEA - Approved by New York City’s Materials and Equipment Acceptance System.
Burglary
• UL
• SIA
Introduction
The System Chart references components evaluated and listed by Underwriters’ Laboratories for compatibility with the
control panel. These components meet the basic system requirements for the applicable standard.
The System Wiring Diagram, Issue A shows the relationship between the panel and the accessory components referred to in
the System Chart.
Optional Compatible Equipment
You can use UL Listed components that do not require evaluation for electrical compatibility in many applications when
installed according to the manufacturer’s instructions.
Burglary Applications
You can use UL Listed burglary alarm sensors that do not require evaluation for electrical compatibility in burglary
applications. In some cases you must use a UL Listed Bosch Security Systems interface module in conjunction with the
sensors. Consult the individual component specification and installation documents to determine suitability.
Test weekly:
UL Standard 1023 requires a weekly test for residential burglary applications.
Auto Arming for Bank Safe/Vault Applications (UL 609)
To auto-arm for Bank Safe/Vault applications, use an Auto On/Auto Off Sked (schedule). Set the Auto On Sked to arm the
system on a 7 day (1 week) timer no later than 10 p.m. Set the Auto Off Sked to disarm the system no sooner than 6 a.m. the
next business day. Adjust these skeds so that the system is armed during non-business hours (such as holidays and
weekends). These times may be adjusted if they conflict with normal business hours and/or any non-business hour carry-
over (extended holiday/closed periods). See Skeds in the D6412/D4412 Program Entry Guide (P/N: 45351) for Sked setup
instructions.
Fire Applications
You can use UL Listed fire initiating devices not requiring electrical compatibility evaluation in any application. For example:
four-wire smoke detectors, heat detectors, water flow switches, and manual pull stations are suitable fire initiating devices.
Consult the individual component specification and installation documents to determine suitability.
Two-wire smoke detectors only connect to the panel on the sensor loop for Location 1. Two-wire detectors must be
evaluated for electrical compatibility, and must be UL listed for use with the panel. See the Bosch Security Systems D6412/
D4412 Technical Service Note: Smoke Detector Compatibility (P/N: 46928), or you may contact the detector manufacturer.
When using four-wire smoke detectors, install a suitable power supervision unit according to the manufacturer’s
instructions. Use the D130 Relay Module, DX3010 Octo-Output
or PO1 to provide reset capability. See Section 9.0 On-Board
Outputs and Section 10.0 Off-Board Outputs for details on the installation of the DX3010.
For battery calculations, refer to Current Rating Chart for Standby Battery Calculations, Standby Battery Requirements, and
Standby Battery Calculation for NFPA 72 Fire Alarm Applications.