D2212B/D2212BE Operation and Installation Guide
D2212B/D2212BE
Page 33
© 2002 Bosch Security Systems
39934E
Appendix C
Appendix C: Installation Guide for UL Applications
Introduction
Table 7 on page 37 references components evaluated and listed by UL for compatibility with the panel. These components
meet the basic system requirements for the applicable standard.
Figure 15 on page 29 shows the relationship between the panel and the accessory components referred to in Table 7. See the
installation and operation instructions for each component for detailed instructions.
Optional Compatible Equipment
You can use UL Listed components that do not require evaluation for electrical compatibility in many applications when
installed in accordance with the manufacturer’s instructions.
Burglary Applications
You can use UL Listed burglary alarm sensors that do not require evaluation for electrical compatibility in burglary
applications. In some cases you must use a UL Listed Bosch Security Systems interface module in conjunction with the
sensors. Consult the individual component specification and installation documents to determine suitability.
In burglary applications with one 7.0 Ah, 12 VDC battery, the panel supports an auxiliary output of 1.0 A and an alarm
(bell) output of 1.35 A, configured as necessary. For additional loadings, refer to Table 6 on page 35.
For commercial burglary installations, use a maximum of 45 sec. of entry delay and a maximum of 60 sec. of exit delay.
Test Weekly:
UL Standard 1023 requires a weekly test. Configure the User System Test to test the battery. See Configuration in
the D2000 Program Entry Guide (P/N: 35114) for instructions.
Fire Applications
You can use UL Listed fire initiating devices not requiring electrical compatibility evaluation in any application. For example:
four-wire smoke detectors, heat detectors, waterflow switches, and manual pull stations are suitable fire initiating devices.
Consult the individual component specification and installation documents to determine suitability.
When using four-wire smoke detectors, install a suitable power supervision unit according to the manufacturer’s
instructions. Use the D133 (or D134) Relay Module to provide reset capability.
In fire applications with one 7.0 Ah, 12 VDC battery, the panel supports an auxiliary output of 140 mA; it supports a total
combined continuous and alarm current draw during alarm conditions of 1.0 A. For additional loadings refer to Table 6.
D132A or D192C required for fire and combined fire/burglary systems:
Fire installations require a D132A Smoke Detector
Reversing Relay Module or a D192C NAC Supervision Module. The alarm output for fire or combined fire/burglary
installations must be supervised. Use a D132A and compatible smoke detectors, or a D192C.
Two-wire detectors must be electrically compatible, and must be UL Listed for use with the D2212. See the Bosch Security
Systems D2000 Series Control/Communicator Technogram (P/N: 35112), or you may contact the detector manufacturer.
Test Weekly:
Bosch Security Systems recommends testing fire and combined fire/burglary systems weekly. Configure the
User System Test to test the battery. See Configuration in the D2000 Program Entry Guide (P/N: 35114) for instructions. For
all burglary applications, the panel must be programmed to send a supervisory signal to the central station a minimum of
once every 24 hrs. Do not set or program an automatic telephone dialer or similar device to place a call to a police station
number that is not specifically assigned by that station for such service.
Sounding Device
The sounding device shall operate for at least 4 min. before an automatic cutoff for household burglary applications and at
least 15 min. for commercial burglary applications.