30
|
Heating circuit data
CFB 840
6 720 802 836 (2012/05)
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Autom adaptation
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 40 Activating Automatic adaptation
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.16 Setting switching optimisation
The following variations are possible:
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Optimisation for
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 41 Setting switching optimisation
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.17 Set switch off optimisation time
If switching optimisation is set to
Switching off
or
Start/Stop
this
option allows the entry of the time when the anticipated setback mode
shall start. The setting must only be changed if so required.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Stop optim. time
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 42 Set switch off optimisation time
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
Input range
Factory setting
Autom adaptation
yes
no
no
Table 54 Setting range Automatic adaptation
The function
Optimisation
requires a remote control
with room temperature sensor to be installed.
The function
Optimisation for
It is not activated in the
factory.
Optimisation Explanation
Start Up
Heat-up commences before the actual switching time
if "Start" has been selected. The control calculates the
start-up time, so that the set room temperature is
achieved at the set switching point.
Switching off When "Switch OFF" has been enabled, the system
begins the setback, where possible, prior to the actual
setback time to save energy. If a room cools down
unexpectedly or suddenly, the stop optimisation is
terminated and heating continues normally up to the
programmed setback time.
Start/Stop
Both optimisation versions are used when "Start/
Stop" has been enabled.
none
Switching optimisation is not implemented if "none" is
selected.
Table 55 Switching optimisation
As the start optimisation is limited to 240 minutes, start
optimisation is not suitable for systems with a long heat-
up time.
HEAT CIRC. DATA 2
Autom adaptation
yes
6 720 802 836-54.1TL
Input range
Factory setting
Optimisation
none
Start
Stop
Start/Stop
none
Table 56 Setting range Optimisation
Input range
Factory setting
Stop optim. time
10 min – 60 min
60 min
Table 57 Setting range Stop optimisation time
HEAT CIRC. DATA 2
Optimisation
for
Stop
6 720 802 836-55.1TL
HEAT CIRC. DATA 2
Stop
optim. time
30min
6 720 802 836-56.1TL