20
|
Boiler parameters
CFB 840
6 720 802 836 (2012/05)
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
The display shows the set value.
Fig. 24 Setting the automatic service date
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
The status of the maintenance message can be scanned in menu
Monitor
. The maintenance message can be reset in menu
Reset
.
8.7
Module selection
On starting the control units or after a system reset, the modules are
automatically recognised and their information downloaded.
Example:
•
Slot 1: ZM424
•
Slot 2: free
However, these modules can also be set manually if required.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Module selection
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Pos. 1
is displayed.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
The display shows the set value.
Fig. 25 Module selection
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
9
Boiler parameters
9.1
Select boiler type
Subject to the selected boiler type, special setting options will be
displayed. For further information regarding the setting of boiler-
specific parameters, see
Æ
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Boiler param.
appears.
B
Press
Display
to call up a submenu.
Boiler type
appears as the first main menu. The display shows the set
value.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
9.1.1 Low temperature boilers
The low temperature boiler is operated with a factory-set pump logic,
which depends on the selected burner type.
Setting the pump logic temperature
The heating circuit circulation pumps and, if installed, the boiler circuit
pump are switched on and off to maintain the boiler operating conditions
subject to the pump logic temperature. The preset pump logic
temperature only needs to be changed in special cases and is only
adjustable in case of boiler type = low temperature.
The factory-set pump logic temperature is 5 K below the minimum
shutdown temperature of the boiler.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Boiler param.
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Pump logic temperature
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
The maintenance message is recorded in the fault log
and can be transferred via the CFB 840 telecontrol
system.
Input range
Factory setting
automatic
maint. message
No
Operating hours
Date
no
Table 20 Setting range Automatic maintenance message
Recommended setting:
Function module none/auto
.
The modules are automatically recognised and installed.
GENERAL PARAM.
maint. message
on
01.10.2012
6 720 802 836-25.1TL
Input range
Factory setting
Boiler type
Low temperature
Ecostream
Condensing
LT/Base line
temperature
Low temperature
Table 21 Setting range Boiler type
MODULE SELECTION
Pos. 1
Function module
none/auto
6 720 802 836-29.1TL