General specification data
|
19
6 720 802 836 (2012/05)
CFB 840
8.4
Remote adjust
The remote adjustment offers the option of external data entry and
adjustment via a remote system.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Remote adjust.
is displayed.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
The display shows the set value.
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
8.5
Manual fault message control
A fault message can be shown in the display of the programming unit
when the manual switch of the function module is set to
Manual
.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Fault message manual control
is
displayed.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
The display shows the set value.
Fig. 22 Manual fault message control
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
8.6
Automatic maint. message
At the user level an automatic maintenance message to appear on the
programming unit display can be generated.
The following settings are possible:
•
Maintenance message by date. Entry of the date of the next service
date (01.01.2000 – 31.12.2088).
•
Maintenance after hours run (only for control units with direct boiler
control).
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
automatic maint. message
is
displayed.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
The display shows the set value.
Fig. 23 Automatic maint. message
B
Release
Display
to save your input.
B
Turn the rotary dial one increment clockwise.
Setting
options
Explanation
yes
Optional remote adjustment via the telecontrol system
no
Remote adjustment is not possible, but system data
can be downloaded and monitored.
Table 17 Setting options Remote adjustment
This parameter cannot be adjusted via the telecontrol
system; it is only intended to be changed in situ.
Input range
Factory setting
Remote adjust.
yes
no
yes
Table 18 Setting range Remote adjustment
GENERAL PARAM.
Fault message
manual control
Fault message
6 720 802 836-23.1TL
If
No
is shown, a warning notice appears if the flap is
closed.
If
Fault message
is shown, an entry also appears in the
fault log. Automatic forwarding via the CFB 840
telecontrol system is then possible.
If
cent. fault mess
is shown, the output of a central fault
message also appears via a volt free contact e.g. via the
FM448/CMB 900-0-10V function module.
Input range
Factory setting
Fault message
manual control
No
Fault message
central fault message
no
Table 19 Setting range Manual switch fault message
The maintenance message "after hours run" is not
possible with this control unit.
GENERAL PARAM.
automatic
maint. message
Date
6 720 802 836-24.1TL