14  I  Commissioning & Warranty details

5 Commissioning 

5.1   Before commissioning

NOTICE:
Do not start the appliance without water!

Only operate the appliance once it has been 
filled with potable water.

•  Ensure the cylinder is filled with water.
•  Check all connections for water tightness.
•  Check the electrical connections.
5.2 Commissioning process
•  Bleed pump according to the process in the pump manual.
•  Ensure all isolation valves are open.
•  Open the hot tap at the furthest point and allow air to bleed 

out until a consistent flow of water is achieved.

•  If a thermostatic mixing valve or a tempering valve is 

attached, set it to the correct temperature.

5.2.1 Commissioning Process - Alphastat Plus
Your AlphaStatPlus has a microprocessor at its core that 
intelligently and automatically controls your hot water system 
at greater efficiency. The AlphaStatPlus measures the cylinder 
water temperature and turns on the pump at the optimum time.
Principle of operation.
The hot water tank sensor is called: ‘TANK’
The upper temperature threshold is called:  
‘SET OFF’ (typically 65° C)
The lower temperature threshold is called:  
‘SET ON’ (typically 60° C)
AlphaStatPlus Display Panel Description.

•  The ‘PWR’ light on indicates that power is being applied to 

the AlphastatPlus.

•  ‘TANK’, ‘SET OFF’ and ‘SET ON’ lights will be on to indicate 

which temperature is being displayed. Only 1 of the 3 can 
be on at a time.

•  The ‘HWC’ light will be on when the hot water circuit (HWC) 

pump is on.

•  The ‘AWAY’ light flashes to indicate that the user has placed 

the controller in a suspended state. No power will be applied 
to the HWC until the ‘AWAY’ button is pressed again to cancel 
it. The AlphaStat will remember the ‘AWAY’ mode even if the 
power goes off and comes on again.

•  The ‘NEXT’ button will step from Tank to Set Off to Set On 

and the display will show the relevant temperature in 

o

C. 

If the Tank sensor is below -20

o

C the display reads ‘Lo’. If 

the Tank sensor is above 140

o

C the display reads ‘Hi’. If the 

sensor is outside the specified temperature range of -40

o

to 150

o

C then the Display will read ‘SSd’ and the ‘NEXT’ 

button is disabled.

•  ‘SET OFF’ and ‘SET ON’ temperatures may be changed 

while they are displayed, by pressing the buttons marked 
with ‘+’ and ‘-’ in yellow (‘HWC’ and ‘AWAY’). The limits are 
20

o

C and 75

o

C, but note that the ‘SET OFF’ temperature 

will always be higher than the ‘SET ON’ temperature. If 
sixty seconds pass and no buttons have been pressed, the 
display reverts to ‘TANK’.

AlphaStatPlus System Adjustable Values.

Installer to fill in at installation time or after any change in 
program Adjustable Values.

System Adjustable Values

Function

AlphaStat-Plus-1 

Factory Value

Installation Values

Set Off

50

o

C

o

C

Set On

35

o

C

o

C

Demand

60

o

C

o

C

Biosafe

60

o

C

o

C

AlphaStatPlus Programming

If the adjustable values from the factory are inappropriate for 
the installation (see included document stating programmed 
values) then the unit needs to be reprogrammed.
Once new values are ‘stored’ they are permanently written into 
memory and will be retained even when power is removed.

Содержание CascadeTherm Plus CT132-1315SS

Страница 1: ...ructions before installing the appliance Please read the operating instructions before commissioning the appliance Please observe the safety instructions in the operating instructions The installation location must meet the manufacturer s requirements Installation must only be carried out by an authorised person Commercial Hot Water 32 ...

Страница 2: ...tion location 9 4 1 2 Positioning the CascadeTherm Plus 9 4 2 Water connections 9 4 2 1 PTR valves supplied with appliance 9 4 2 2 Temperature mixing device 10 4 2 3 Pressure limiting valve 10 4 2 4 Expansion control valve 10 4 3 Gas connections 11 4 4 Electrical connections 11 4 4 1 Electrical Wiring 11 4 5 Fluing Requirements 11 5 Commissioning 14 5 1 Before commissioning 14 5 2 Commissioning pr...

Страница 3: ...nal injury DANGER indicates a risk to life Important information Important information where there is no risk to people or property is indicated with the adjacent symbol It is bordered by lines above and below the text Additional symbols Symbol Meaning 3 Action step k Cross reference to other parts of this document or to other documents List list entry 1 2 Safety Instructions DANGER Water temperat...

Страница 4: ...ARNING Water temperatures over 50o C can cause severe scalds Local regulations and or the requirements of AS NZ 3500 4 must be considered regarding the temperature limitations of hot water used primarily for personal hygiene Notice to Victorian Customers from the Victorian Plumbing Industry Commission This water heater must be installed by a licensed person as required by the Victorian Building Ac...

Страница 5: ...nd AlphastatPlus controller attached The following parts of the standard delivery are packed separately Pressure temperature relief PTR valve x 2 Technical documentation Commercial Hot Water 32 Fig 1 1 Bosch CascadeTherm Plus 2 Installation instructions including operating instructions for the pump gas burner and thermostat 3 PTR valve x2 1 2 3 ...

Страница 6: ...greater efficiency Primary circuit pump The Grundfos UPS 25 80N pump is included as the primary circuit pump 2 2 2 Description of Operation The Grundfos UPS 25 80N pump is used to circulate water from the tank through the water heater When the Senztek thermostat activates the pump the movement of water through the flow sensor of the water heater sends a signal to the electronic control unit This s...

Страница 7: ...kW Approximate mass full 420 kg Approximate mass empty 100 kg Maximum temperature 75o C Water Heater KM3211WHNG Minimum water pressure for maximum flow 200kPa Minimum flow rate 3 5L min Gas consumption NG 250MJ h LP 250MJ h Power supply 240V 50Hz Pump GRUNDFOS UPS 25 80N Connections Water 25mm Electrical Connection 240V 50Hz Thermostat AlphastatPlus Position Description Measurement A Cold inlet 32...

Страница 8: ...ten the life of the water heater and may endanger life and or cause property damage The manufacturer disclaims any responsibility for such loss and or injury resulting from the use of such unauthorised devices CAUTION The Bosch KM3211WHNG LP is an internal with fluing or external appliance electronically controlled gas boosted water heater It comes supplied and preset to deliver water at a tempera...

Страница 9: ...ift the CascadeTherm Plus from the pallet and position it on a level floor that has adequate load bearing capacity 4 2 Water connections WARNING All plumbing work must be carried out by a qualified professional and in accordance with the Plumbing Standard AS NZS 3500 4 and local authority requirements Installation of the water inlet or outlet pipes The water inlet and outlet thread are 32mm BSP in...

Страница 10: ...alves comply with this WARNING Never block or seal the outlet of the PTR valve or its drain for any reason The warranty will be void if the relief valves or other safety devices are tampered with or if the installation is not in accordance with this manual Connect the outlet of the relief valve to a suitable open drain so that the discharge water cannot contact any electrical parts persons or anim...

Страница 11: ...ons This appliance requires two 240V general purpose power outlets one for the water heater and one for the thermostat 4 4 1 Electrical Wiring Employ a qualified electrician for the electrical work The electrical supply required by both the water heater and the thermostat is 240V AC at 50 Hz the power consumption may be up to 135W Use an appropiate circuit Do not disconnect the power supply when n...

Страница 12: ...pipe before the first elbow Available flue components Components Part No Description KMVC 100 Vent Cap FKV32LTR Vertical Flue Kit FKH32LTR SS flue elbow 90 100m diameter Outdoor installation Components Part Numbers KMVC 100 Maximum length mm no of components required N A 1 Standard vertical flue kit Part No 100mm FKV32LTR Maximum length mm no of components required 9m 1 kit Standard horizontal flu...

Страница 13: ...solation valve Non return valve Pressure limiting valve Filter in line Legend Gas Meter Pressure relief valve Tundish Pump Connectors Commercial Hot Water 32 Fig 6 Typical layout for manifolded CascadeTherm Plus Commercial Hot Water 32 Commercial Hot Water 32 Fig 7 ...

Страница 14: ...t water circuit HWC pump is on The AWAY light flashes to indicate that the user has placed the controller in a suspended state No power will be applied to the HWC until the AWAY button is pressed again to cancel it The AlphaStat will remember the AWAY mode even if the power goes off and comes on again The NEXT button will step from Tank to Set Off to Set On and the display will show the relevant t...

Страница 15: ...n the AlphaStat and forcing the burner to high by pressing Max Pressure Set Button Refer to Fig 8 Circuit Board Manifold Pressure Increase Button Manifold Pressure Decrease Button Minimum Pressure Set Button Maximum Pressure Set Button Figure 8 Check table for correct inlet gas pressure NG LP KM3211WH 1 13 2 75 The appliance must be disconnected from the gas supply piping during any pressure testi...

Страница 16: ...nsumer Law statement If you have purchased your product in Australia you should be aware that This warranty is provided in addition to other rights and remedies held by a consumer at law Our goods come with guarantees that cannot be excluded under the Australian Consumer Law You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable lo...

Страница 17: ...oduct installed to supply hot water for use by individuals in domestic dwellings For Product used for all other uses the commercial use warranty period will apply This includes without limitation installations such as centralised or bulk hot systems hotels sporting complexes caravan parks laundry facili ties restaurants and cafes For Parts only warranty the end user will be charged for service cal...

Страница 18: ...roduct in accordance with recommendations in instruction manuals for Product may result in a warranty claim under this voluntary warranty being rejected by Bosch Bosch alerts end users that instruction manuals for Product contain specific recommendations for servicing and safety checks to be carried out on Product Table 9 Warranty Exclusions This warranty will not apply to a defect or fault to the...

Страница 19: ...concerns within and outside the warranty period Bosch is well aware of its product liability and product safety obligations and responsibilities It is our aim to ensure appropriate product safety standards are met in order to avoid injury loss and damage caused by defects in any Product Privacy Bosch is required to seek personal information from an end user who seeks to make a claim under this war...

Страница 20: ... au New Zealand Sales Hotline 0800 54 33 52 Sales Fax 0800 54 33 55 www bosch climate co nz Technical data subject to modification without notice Printed in Australia Any color variations are due to the limitations of the printing process Printed on 100 chlorine free bleached cellulose manufactured in an environmentally friendly process ...

Отзывы: