8.6.4 Open circuit or short circuit of temperature sensor
(E4 (outdoor) / F1 / F2 / F3 / F4/ F5 (indoor))
Error Code
E4 (outdoor) / F1, F2, F3, F4, F5 (indoor)
Malfunction decision conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Supposed causes
f
Improper / Incorrect Wiring
f
Sensor faulty
f
Indoor / Outdoor PCB faulty
Table 22
Troubleshooting:
Figure 49
Check the connections
between temperature
sensor and PCB.
the connections correct?
Correct the connections.
No
Yes
Yes
Replace indoor or outdoor PCB.
Replace the sensor
Check the resistance value
of the sensors via Appendix 1
and Appendix 2
Is it normal?
No
Figure 50