Figure 4.17: Location of the Wiegand interfaces for external devices
These interfaces are point-to-point connections, and each can
support only a single reader with a maximum cable length of
90 m (300 ft) for 24 AWG or 150 m (500 ft) for 22 AWG. Readers
are addressed according to their respective interface numbers.
Refer to Connecting Diagrams, page 60 for a complete wiring
diagram of the Wiegand reader interface .
Connecting Relay Outputs
To operate locks or alarm systems, the AMC2-4W has eight form
C relay outputs. The outputs will be connected to the 3-pin
pluggable screw connectors S5, S6, S10, S11, S17, S18, S22,
and S23 - refer to Connecting Diagrams, page 60.