Address
DIL Switches
1
2
3
4
None
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
3
ON
ON
OFF
OFF
4
OFF
OFF
ON
OFF
5
ON
OFF
ON
OFF
6
OFF
ON
ON
OFF
7
ON
ON
ON
OFF
8
OFF
OFF
OFF
ON
Table 4.1: Setting the address via the DIL switch
Instructions for DIL switch 5
Set SDEB (= DIL switch 5 to ON) in the following cases
–
Ethernet host connection
–
RS-485 host connection, provided only one AMC2 is
connected on the bus
Set BPA (= DIL switch 5 to OFF) in the case of an
–
RS-485 host connection with more than one and maximum
eight AMC2s per bus
Notice!
Changing the type of the host connection requires a reset of
the AMC2 - see Resetting the Software, page 52.