44
en | Installing
AMC2 4W | Installation manual
F.01U.024.965 | V 0.1 | 2006.03
Bosch Sicherheitssysteme GmbH
5.11
Connecting Relay Outputs
To operate locks or alarm systems the AMC2 4W has eight form
C relay outputs. The outputs will be connected to the 3-pin
pluggable screw connectors: S5, S6, S10, S11, S17, S18, S22,
and S23.
Fig. 5.19
Location of the relay output connectors
Each relay output can operate in ‘wet’ mode, using the AMC2
4W's internal 12V DC power supply for external devices or ‘dry’
mode with potential free contacts for externally powered sys-
tems.