18
en | Connections
AMC2 enclosure with 1
DIN rail
2020-07 | V04 | F.01U.330.018
Bosch Security Systems B.V.
3.3.2
24 V mode operation
Notice!
Make sure that the power supply has the correct output voltage
(24 V).
+
-
+
-
B12
C1
B7a
B7b
Figure 3.4:
24 V mode
Connecting the battery cables
1.
Set the switch of the power supply unit to 24 V.
2.
Connect B12 to the power supply interface labeled BAT.
3.
Connect B7a (red) to the positive (+) pin of the first
rechargeable battery.
4.
Connect B7b to the negative (-) pin of the second
rechargeable battery.
5.
With cable C1 (black), connect the negative (-) pin of the
first rechargeable battery to the positive (+) pin of the
second rechargeable battery.
6.
Attach the connectors B8a and B8b to the bracket
.