Assembly
W 120-5 O – 6 720 819 306 (2018/10)
27
5.2.1
Connecting the DHW cylinder on the water side
System schematics with all recommended valves (
▶ Use installation material that is heat-resistant to 160 °C (320 °F).
▶ Never use open, vented expansion vessels.
▶ Use metal connection fittings in potable water heating systems with
plastic lines.
▶ Size the drain line in accordance with the connection.
▶ To facilitate debris removal, never install elbows in the drain line.
▶ If using a non-return valve in the cold water supply: Install a pressure
relief valve between the non-return valve and cold water inlet.
▶ Install a pressure reducer if the static system pressure is in excess of
5 bar.
5.2.2
Installing a pressure relief valve (on site)
▶ Install a type-tested pressure relief valve on site that is approved for
potable water (
DN 20) in the cold water supply (
▶ Observe the pressure relief valve installation instructions.
▶ Terminate the discharge pipe of the pressure relief valve where it will
be easily visible in the frost-proof area via a dewatering point.
– The discharge pipe must be at least equal to the outlet cross-
section of the pressure relief valve.
– The discharge pipe must be able to discharge at least the flow rate
that is feasible at the cold water inlet (
▶ Attach a notice with the following text to the pressure relief valve:
"Never close the discharge pipe. During heating, water may be
discharged for operational reasons."
If the static system pressure exceeds 80 % of the pressure relief valve
excess pressure:
▶ Install a pressure reducer upstream (
5.3
Installing the hot water temperature sensor
Install the hot water temperature sensor at the test point [4] to measure
and monitor the DHW temperature in the DHW cylinder
(
▶ Install the hot water temperature sensor (
Ensure that the sensor surface has contact with the sensor pocket
surface over its full length.
Item
Description
1
Storage cylinder
2
Air vent valve
3
Shut-off valve with drain valve
4
Pressure Relief Valve
5
Non-return valve
6
Stop valve
7
DHW circulation pump
8
Pressure reducer valve (if required)
9
Test valve
10
Non-return component
11
Pressure gauge connector
AB
DHW outlet
EK
Cold water inlet
EZ
Circulation inlet
Table 7 System schematics (
Gas supply
pressure
(static
pressure)
Pressure relief
valve excess
pressure
Pressure reducer
in the EU
outside the EU
< 4.8 bar
6 bar
not required
5 bar
6 bar
max. 4.8 bar
5 bar
8 bar
not required
6 bar
8 bar
max. 5.0 bar
not required
7.8 bar
10 bar
max. 5.0 bar
not required
Table 8 Selection of a suitable pressure reducer