background image

6 720 644 942

Installation instructions

9

3.4

Combustion air requirements

The  Protankless  water  heater  holds  cold  water  in  its
copper heat exchanger and water valve when not in use.
Because of this, any cold air that comes down through
the  unit's  vent  pipe  is  capable  of  freezing  these
components.  This  Installation  Manual  specifies  the
minimum  vertical  vent  pipe  and  the  amount  of
combustion  air  required  for  this  unit.  When  all
requirements are followed, the unit will operate properly
and safely. However, there may still be a risk of freezing
due to negative draft if all the combustion appliances in
the  structure  are  not  being  supplied  with  sufficient
combustion  air.  A  wood  stove  or  furnace  can  pull  it's
combustion  air  from  the  Protankless  vent  pipe.  This
allows  the  cold  infiltrating  air  to  potentially  freeze  the
cold  water  in  the  AquaStar  heater.  Damage  from
freezing  is  not  covered  under  the  manufacturer's
warranty.  Supplying  more  combustion  air  for  all
combustion  appliances  is  the  solution.  Follow  the
instructions  on  venting  and  checking  adequacy  of
combustion air. A HVAC specialist should be consulted
to  design  solutions  for  providing  more  make-up  air  if
necessary.  Observe  the  following  instructions
concerning combustion air.

Appliances located in unconfined spaces:

a)

 An unconfined space is one whose volume is greater

than  50  cubic  feet  per  1000  Btu  per  hour  of  the
combined rating of all appliances installed in the space.
That would be 5850 cubic feet for the Protankless 520
HN alone.

b)

  Installations  in  structures  that  have  been  tightly

constructed  (air  infiltration  rate  of  0.40  ACH  or  less)
must be provided with combustion air per the National
Fuel Gas Code.  Consult a HVAC specialist if your air
infiltration rate is questionable.

Appliances located in confined spaces:

The  confined  space  must  be  provided  with  two
permanent  openings,  one  commencing  within  12
inches of the top and one commencing within 12 inches
of the bottom of the enclosure. Each opening must have
a minimum free area of one square inch per:

• 1000 Btu/hr if all air is taken from inside the building.

• 2000  Btu/hr  if  all  air  is  taken  from  the  outside  by

horizontal ducts.

• 4000  Btu/hr  if  all  air  is  taken  from  the  outside  by

direct openings or vertical ducts.

Or  the  confined  space  must  be  provided  with  one
permanent opening or duct that is within 12 inches of
the ceiling of the enclosure. This opening must have a
minimum free area of one square inch per:

• 3000 Btu/hr if all air is taken from the outside by a

direct opening or vertical duct.

Louvers, grills and screens have a blocking effect. If the
effective  free  area  is  not  known,  increase  the  sizes  of

your openings by 400% if your louvers are wood and by
135%  if  your  louvers  are  metal.  Refer  to  the  National
Fuel Gas Code for complete information. In buildings of
tight construction all air should be taken from outside.

3.5

Mounting Heater

The 520 HN is approved for installation on a combusti-
ble wall provided the floor covering below the heater is
noncombustible. For installations in an alcove or closet,
maintain  the  minimum  clearances  to  combustible  and
non-combustible materials listed in Fig. 4.

Remove cover and inspect.

B

Remove  the  flow  control  and  power  adjustment
knobs.

B

Unsrew the cover fixing screws, see Fig. 10.

B

Loosen  the  two  Phillips  head  screws  located  on
bottom  rear  of  cover.  Remove  cover  by  pulling  it
outward and then lifting upwards.

B

Ensure that the flue terminal is clear.

B

After  inspection,  replace  front  cover  and  tighten
screws.

Install incandescent particle tray.

B

Install  incandenscent  particle  tray  using  screws
provided as shown in Fig. 9.

Fig. 9

Incandescent particle tray illustration

Warning: 

before starting installation:

B

check  that  there  are  no  loose  parts
inside the appliance

B

ensure  that  gas  pipe,  gas  valve,  and
burner  have  no  damage  and  are
properly fitted.

B

Read chapter 2.2 to verify proper gas 
type and to verify all parts are included 
in box.

i

Front cover must be removed in order to
inspect 

components 

visually 

(see

instructions below).

Incandescent particle tray

Screws

Содержание 520-HN-L

Страница 1: ... or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier In the Commonwealth of Massachusetts this product must be installed by a licensed plumber or gas fitter Upon completion of the installation these instructions should be handed to the user of the appliance for future reference What to do if you smell gas...

Страница 2: ...ppears when hot water is turned on but pilot and burners will not ignite 19 6 4 Pilot lights but burners will not come on 20 6 5 Main burners go out during hot water use 20 6 6 Hot water temperature fluctuates at tap 21 6 7 Water is too hot 21 6 8 Water is not hot enough 22 6 9 Low hot water pressure 22 6 10 Noise when heater is running 22 6 11 Burners do not burn cleanly yellow flames when operat...

Страница 3: ...tivate heater 0 5 gallon minute 1 9 l m Minimum recommended water pressure 30 PSI 2 07 bar Connections Bottom of heater Temperature rises 1 45F rise 4 1 gpm 50F rise 3 7 gpm 55F rise 3 4 gpm 65F rise 2 8 gpm 77F rise 2 4 gpm 90F rise 2 0 gpm Dimensions Depth in 8 66 220 mm Width in 16 73 425 mm Height in 25 75 655 mm Weight 35 pounds 16 kg Gas types Natural Gas LP Gas Safety devices Flame failure ...

Страница 4: ... with local codes or in the absence of local codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 In Canada The Installation must conform with CGA B149 1 2 INSTALLATION CODES and or local installation codes 2 Carefully plan where to install the heater Proper clearances must be followed 3 The appliance must be isolated from the gas supply piping system by closing its individual manual gas shutoff v...

Страница 5: ...37 Mounting holes 38 Exhaust pipe union 39 Draft diverter with flue gas sensor 40 Gas valve Fig 4 Minimum clearances 39 38 4 5 23 11 40 H 6720608036 01 2Av 8 66 220 E F G 4 92 125 D 2 50 63 5 1 97 50 3 82 97 A B 37 10 26 35 34 20 36 C Model 520 HN TOP A 12 inches 306 mm FRONT B 4 inches 100 mm BACK 0 inches SIDES 4 inches 100 mm BOTTOM C 12 inches 306 mm Dimensions inches mm 520 HN A 16 73 425 B 2...

Страница 6: ...ntal venting An AQ4 powervent with a proof of draft safety interlock device is required and is available for sidewall venting Contact your dealer In the Commonwealth of Massachusetts power vented applications must utilize proof of draft safety interlock device and comply with regulations established for all side wall horizontally vented gas fueled equipment 3 3 2 Vertical venting B A 5 inch diamet...

Страница 7: ...ance with Fig 7 and table 2 provided they are at least 8 feet 2 4 m from a vertical wall or similar obstruction All other gas vents that are not able to terminate within the minimum specified height allowed must terminate not less than 2 feet 0 6 m above the highest point where it passes through the roof and at least 2 feet 0 6 m higher than any vertical wall or similar obstruction within 10 feet ...

Страница 8: ...k local codes for clarification The lining material must be listed for use only with naturally drafting draft hood equipped gas appliances Follow manufacturer s instructions for installation of listed lining material You may not vent any other fuel burning appliances into any free space remaining in the chimney The minimum vertical gas vent length within the masonry chimney must be no less than 5 ...

Страница 9: ...2 inches of the bottom of the enclosure Each opening must have a minimum free area of one square inch per 1000 Btu hr if all air is taken from inside the building 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Or the confined space must be provided with one permanent opening or duct that is ...

Страница 10: ... either 1x4 s or 1 2 minimum plywood first be attached across a pair of studs and then the heater should be attached to the support boards See Fig 11 B Install the two included L shaped hooks to wall studs or support board 13 apart See Fig 11 B Hang heater on two L shaped hooks See Fig 12 Fig 10 Remove front cover Fig 11 Support board Fig 12 Secure heater to wall Warning B Do not install this appl...

Страница 11: ... for leaks HIGH ALTITUDE INSTALLATION The pressure regulator provided with the heater has been adjusted to deliver the proper gas pressure as indicated on the rating plate and in the manual for altitude up to 2000 feet 660 meters above sea level On appliances being installed above 2000 ft 660 meters elevation the inlet gas pressure should be adjusted at installation to the value shown below Note T...

Страница 12: ... Pressure Drop of 0 5 Inch Water Column EHD Equivalent Hydraulic Diameter The greater the value of EHD the greater the gas capacity of the tubing Nominal Iron Pipe Internal Size Diameter inches inches 10 20 30 40 50 60 70 80 90 100 125 150 175 200 3 4 0 824 278 190 152 130 115 105 96 90 84 79 72 64 59 55 1 1 049 520 350 285 245 215 195 180 170 160 150 130 120 110 100 1 1 4 1 380 1050 730 590 500 4...

Страница 13: ...odes if more stringent Never sweat any rigid piping directly to or beneath the water connections or damage can occur to the internal water valve from heating of the pipe Plastics or other PEX type plumbing line materials are not allowed for connecting directly to the water heater Keep water inlet and outlet pipes to no less than 12 7mm diameter to allow the full flow capacity It is recommended tha...

Страница 14: ...on for lighting the pilot and main burners When turning the heater on follow these instructions exactly B Before operating the unit set the On Off button to the On position The On Off button is located on the front panel Smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS B Clos...

Страница 15: ...lot flame will extinguish a few seconds after the burners come on The burners will remain on until the hot water tap is turned off Note The 520 HN operates in two modes See SETTING THE WATER TEMPERATURE 4 3 To turn off appliance B Set the ON OFF switch to the position OFF Fig 19 B Close installer supplied manual gas shutoff valve on the supply line to the heater 4 4 Adjusting the water temperature...

Страница 16: ...ob clockwise sup plies less gas to the burners and lowers the water temperature Fig 22 B Turning the power adjustment knob counter clock wise supplies more gas to the burners and raises the water temperature Fig 23 Maximum temperature The maximum temperature is achieved by turning the left power adjustment knob fully counter clockwise and the right flow control knob fully clockwise 4 6 Draining th...

Страница 17: ...by removing the retaining clip on water valve assembly and pulling the pipe free from the water valve Loosen the two set screws underneath the water valve where it connects to the gas valve If the set screws are seized STOP and call Bosch tech support before proceeding Forcing and breaking seized set screws may damage the water valve and gas valve assemblies Remove the water valve by pulling it to...

Страница 18: ...e pressure from the plumbing system 3 Drain water from the unit by disconnecting inlet and outlet water connections 4 Connect the line A from the outlet of the circulating pump installer supplied to the inlet water fitting on the water heater 5 Using another line B connect to the water outlet fitting on the water heater Route the other end of this line into a descaling reservoir 6 Using a 3rd line...

Страница 19: ...lean wire connections in heater a wire from ignition unit to spark electrode b wires to flue gas sensor on draft diverter c wires to overheat sensor on outlet pipe d wires to overheat sensor on heat exchanger e wires to microswitch f ground wire connection between ignition unit and fixing screw 8 If a powervent and spill switch are installed check the reset button on the spill switch installed on ...

Страница 20: ... the pilot orifice may be dirty or clogged See chapter 5 3 on how to clean the pilot and orifice 3 If sparking does not stop when pilot is lit the flame sensor may not be recognizing pilot flame Verify that wire connection clip on wire from the bottom of the flame sensor is secure If flame sensor is fully engulfed by the pilot flame it may be dirty Clean entire surface area of flame sensor with a ...

Страница 21: ...rning the gas control knob clockwise for lower hot water temperatures See chapter 4 5 If the problem persists go to www boschpro com for service bulletin CT 07 4 The water heater is designed to modulate gas flow to the burners when water flow varies If the water pressure in the home is erratic and the water flow is not consistent while a tap is opened then the temperature of the hot water will flu...

Страница 22: ...e unit Place a gallon jug under hot water outlet to catch water Open cold water supply and measure flow rate out of the unit With temperature adjustment knob set all the way clockwise the flow rate should be close to 2GPM filling the jug in 30 seconds or less If the flow rate is not adequate inspect and clean inlet filter screen See chapter 5 2 2 Confirm that the incoming water pressure to the uni...

Страница 23: ...out the disposal of recyclable products Saving water resources B Make sure you close all the taps after any use Avoid leaving the taps dripping Repair any leaking tap B Define the temperature you want This way you have the precise water flow needed mixing cold water to regulate temperature will increase the water flow with consequent waste of water For increased safety shut off the appliance from ...

Страница 24: ...list 8 1 Interior components Fig 27 Functional scheme 4 Heat exchanger 5 Burner 9 Ignition unit 10 Flow control knob 11 Water valve 20 Gas connection 21 Flexible cold inlet 22 Flexible hot outlet 26 Power adjustment knob 30 Pilot burner 51 on off button 4 5 11 20 10 22 26 51 9 30 6720608036 04 3AL 21 ...

Страница 25: ...agram parts list 25 8 2 Components diagram Fig 28 Components Diagram 12 50 40 10 11 8 6 7 21 22 42 35 31 33 36 39 45 20 19 15 14 13 16 17 18 43 46 47 36 48 49 2 1 3 5 4 28 29 30 6720608036 05 3 JF 53 23 24 38 41 34 32 37 27 25 26 44 51 52 54 ...

Страница 26: ...ressure regulator NG 8 707 406 084 0 23 Water valve 8 707 006 344 0 24 Watervalve pushrod 8 703 204 051 0 25 Diaphragm 8 700 503 084 0 26 Inlet water connection 8 700 306 110 0 27 Selector screw 8 708 500 304 0 28 Ignition unit 8 707 207 272 0 29 Cable 8 704 404 060 0 30 Flue gas sensor 8 707 206 446 0 31 Heat exchanger washer 8 700 103 658 0 32 Threaded bushing 8 700 306 148 0 33 Connector 8 700 ...

Страница 27: ...upplying the replacement part s Bosch Thermotechnology Corporation will provide ground service delivery for these parts Expedited or upgraded shipping will be charged to the customer Service Labor Costs This warranty does not cover any labor costs associated with service removal or re installation of part s All such costs must be borne by the Purchaser Additionally this warranty does not cover any...

Страница 28: ... side panel Gas Pressure Reading Static__________ Operating__________ Building Water Pressure __________ Range if on Well system __________ Average Winter Temperature __________ Average Summer Temperature __________ Installing Company _____________________________________________ Installer name _____________________________________________ Address _____________________________________________ Phon...

Отзывы: