5. Connection and Operation

 

 

 
 
 

5.1 Inspection:   

Inspect  the  packaging  carton  and  its  contents  for  damage.  Please 
inform  the  transport  agency  immediately  should  you  find  signs  of 
damage. 

Please keep the packaging in a safe place for future use. 

5.2 Connection: 

(1) UPS Input Connection 

If the UPS is connected via the supplied input power cable, please 

connect to a socket which has necessary protection and capacity: 

over 6A for B400-010-B and B400-010-C, over 7A for B400-020-B, 

13A for B400-020-C, B400-030-B, and B400-030-C.   

If  the  UPS  is  being  hardwired,  the  correct  cable  and  protective 

safety device should be selected. 

When selecting the protective device, the user can refer to below 

table for detailed information when installation. 

UPS INPUT ISOLATOR 

Model No. 

VOLTAGE 

CURRENT 

B400-010-C 

240 VAC 

10A 

B400-020-C 

240 VAC 

20A 

B400-030-C 

240 VAC 

32A 

If electrical wiring is required the system must be installed to 
local safety standards by qualified electricians. 

www.upsdirect.com

Содержание B400-010-B (C)

Страница 1: ...UPS B400 Online UPS B400 Online UPS B400 Online UPS User Manual B400 010 B C B400 020 B C B400 030 B C 200 208 220 230 240VAC w w w u p s d i r e c t c o m support upsdirect com 44 0 8456 445 002 www upsdirect com ...

Страница 2: ...tion 12 5 1 Inspection 12 5 2 Connection 12 5 3 Battery charge 14 5 4 Turn on the UPS 14 5 5 Test function 15 5 6 Turn off the UPS 15 5 7 Audible alarm mute function 15 5 8 Operation procedure of external battery for long backup time model C model 15 6 Operating Mode for All Models 17 6 1 Online mode 18 6 2 Battery mode 19 6 3 Bypass mode 20 6 4 NO output mode 21 6 5 EPO Emergency Power Off 21 6 6...

Страница 3: ...8 9 Technical Data 29 9 1 Electrical specifications 29 9 2 Operating Environment 29 9 3 Typical backup time Typical values at 25 C in minutes 30 9 4 Dimensions and weights 30 10 Communication Port 31 10 1 USB 31 10 2 RS232 Interface Option 31 10 3 AS400 Interface Option 32 11 Software 33 Appendix Rear panel 34 w w w u p s d i r e c t c o m ...

Страница 4: ...ould be exposed to direct sunlight or near a heat source Do not connect items of equipment which would overload the UPS e g laser printers to the UPS output Always place cables in such a way so that they are not a trip hazard Always make sure the installation is connected to a reliable earth source Any additional battery cabinets must be connected to a reliable earth source Check after installatio...

Страница 5: ...not disconnect the mains cable to the UPS during operation as this would remove the earthing point of the UPS and of all connected loads The UPS may have internal batteries electricity maybe present at the output terminals of the UPS even with the mains disconnected In order to completely isolate the UPS first press the OFF button to turn off the UPS then disconnect the mains lead Ensure that no l...

Страница 6: ...a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessary when working with batteries remove all jewellery wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries replace with the same quantity and the same type of batteries Dispose of all batteries according to l...

Страница 7: ...rrent IEC EN 61000 3 2 Voltage Fluctuation and Flicker IEC EN 61000 3 3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 11 Low Frequency Signals IEC EN 61000 2 2 w w w u p s d i r e c t c o m ...

Страница 8: ... 5 2 Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual Please familiarize yourself with them w w w u p s d i r e c t c o m ...

Страница 9: ...age which permanently supplies the loads The connected load is thus powered entirely by the UPS inverter voltage In the event of power failure the maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm it is the correct manual by checking the model number on the rear panel of the UPS B Model Internal battery C Model Internal charger for extended b...

Страница 10: ...this button when mains power is normal the UPS will switch to Bypass mode the inverter is also switched off If Bypass is enabled then the output sockets are supplied with mains unprotected mains voltage if mains power is available Pressing this button while the UPS is in bypass mode will deactivate the acoustic alarm Select Button Enter Button These buttons are reserved for Borri service engineers...

Страница 11: ...tes the input mains line current value which could be displayed from 0 to 99 9A Indicates the input mains line voltage is higher than the specification value and the UPS would switch the battery mode Indicates the input mains line voltage is lower than the specification value and the UPS would switch to battery mode Indicates the input mains line voltage is within normal specification and the UPS ...

Страница 12: ...cuit and the UPS would in fault mode Indicates the UPS is being overloaded Indicates the load percentage each box representing 25 increments Indicates the load percentage W is displayed when the load is displayed in watts or VA is displayed when the load is displayed in VA Voltage Ampere The display will change depending which value is the higher Battery Information Indicates the battery voltage v...

Страница 13: ...s working in bypass mode the load is directly supplied by the input mains power through bypass Indicates the UPS is working normally in online mode Indicates the UPS is working in battery mode Indicates the UPS is working in fault mode Indicates there are warnings that need attention Indicates there are no warnings or fault conditions UPS setting Information The value with the bullet on the left h...

Страница 14: ...utput frequency This can be changed on request or by Borri service engineers The value with the bullet on the left hand side shows whether the bypass function is enabled or disabled This can be changed on request or by Borri service engineers w w w u p s d i r e c t c o m ...

Страница 15: ...tion and capacity over 6A for B400 010 B and B400 010 C over 7A for B400 020 B 13A for B400 020 C B400 030 B and B400 030 C If the UPS is being hardwired the correct cable and protective safety device should be selected When selecting the protective device the user can refer to below table for detailed information when installation UPS INPUT ISOLATOR Model No VOLTAGE CURRENT B400 010 C 240 VAC 10A...

Страница 16: ... 020 B C 6 IEC type B400 030 B C 5 IEC type 4 x 10A 1 x 16A 3 EPO Connection User can select the polarity of EPO EPO is Normally close as default setting Normally open Normally the EPO connector is open on the rear panel Once the connector is closed with a wire the UPS would stop the output until the EPO status is disabled Disable the EPO status Enable the EPO status Caution Do not connect equipme...

Страница 17: ...e however the specified full backup time may not be achieved 5 4 Turn on the UPS 1 With mains power connected Press and hold the I button to turn on the UPS the UPS will go into inverter mode and the LCD screen will indicate the state of the UPS 2 Without mains power connected If the UPS is required to be started without mains power available Cold Start the user will need to press the I button twi...

Страница 18: ... alarm can be silenced while the UPS is in battery mode by pressing and holding the I button The alarm will be enabled when the battery charge is at low level to alert imminent shutdown of the UPS The audible alarm can be silenced while the UPS is in bypass mode by pressing and holding the button The action doesn t affect the warning and fault alarm 5 8 Operation procedure of external battery for ...

Страница 19: ...nal of the battery and black is the terminal of battery the green one is the earth Because the connector is ANDERSON type the wires which is used to the connector should be the same type Note the green yellow wire is grounded for protection purpose 6 Connect the cable to the UPS and battery box 7 Turn on the UPS the batteries will then start to be charged DC breaker Model No VOLTAGE CURRENT B400 0...

Страница 20: ...ted in the table below Under normal circumstances only one code will appear If warnings are present the appropriate codes will scroll through Normal operating mode Code No output mode 0 Bypass mode 1 Line mode 2 Battery mode 3 Battery test mode 4 ECO mode 5 Converter mode 6 w w w u p s d i r e c t c o m ...

Страница 21: ...d switch off unnecessary load one by one to decrease the load connected to the UPS ideally less than 90 of its nominal power capacity Note Please see following if running the UPS from a diesel generator Activate the generator and wait for the engine to stabilize before supplying power to the UPS Turn on the UPS according to the start up procedure After the UPS is turned on then the loads can be co...

Страница 22: ...panel is pressed for more than 1 second the alarm will stop beeping in silence mode Press the ON button once again for more than 1 second to resume the alarm function 2 If the UPS is running in battery mode because the mains input line voltage is higher than the maximum specification the alarm symbol High will be shown if the UPS is running in battery mode because the mains input line voltage is l...

Страница 23: ... UPS output and the load is displayed The UPS will beep once every 2 minutes while in bypass mode The Bypass and 1 code indicate the UPS is working in the bypass mode The UPS will not support the load while in bypass mode The power used by the load is supplied from the mains power via internal filter and is unprotected Bypass mode w w w u p s d i r e c t c o m ...

Страница 24: ...No output mode 6 5 EPO Emergency Power Off It is also called RPO Remote Power Off On the LCD display the mode code is 0 the word EPO is presented in the position of output voltage It is a special status in which the UPS would switch the output off and alarm The UPS cannot be turned off by pressing the OFF button on the panel until the EPO has been released by turning or releasing the EPO switch No...

Страница 25: ...ode In converter mode the UPS LCD will display the mode code 6 The UPS would run with a fixed output frequency 50Hz or 60Hz in converter mode Once the mains power is lost or abnormal the UPS would transfer to battery mode and the load is supplied continuously by the battery 1 This mode can be enabled through the LCD setting or software 2 The load should be derating to 60 in converter mode 6 8 Abno...

Страница 26: ...0 Bypass mode 1 Line mode 2 Battery mode 3 Battery test mode 4 ECO mode 5 Converter mode 6 Warning Code Site fail 09 Fan fail 10 Battery over voltage over charged 11 Battery low 12 Charge fail 13 DC DC temperature high 21 Inverter temperature high 24 Ambient temperature high 25 Line voltage high OVCD action 26 Battery open 27 w w w u p s d i r e c t c o m ...

Страница 27: ...stem is connected to mains power supply No input voltage Check building wiring socket outlet and input cable BYPASS LED lights up even though the power supply is available Inverter is not switched on Press On Switch I BATTERY LED lights up and audible alarm sounding every 1 beep in every 4 seconds Mains power supply has failed or Input power and or frequency are out of tolerance Switching to batte...

Страница 28: ...ow When the audible alarm is sounding every second the battery is almost empty Charge fail The charger is broken Notify dealer DC DC temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature Inverter temperature high Inside temperature of the UPS is too high Check the ventilation of the UPS check the ambient temperature of the room Am...

Страница 29: ...unction is enabled Turn off the EPO switch Bus fault UPS internal fault Notify dealer Inverter fault UPS internal fault Notify dealer Over temperature fault Over temperature Check the ventilation of the UPS check the ambient temperature and ventilation Inverter short Output short circuit Remove all the loads Turn off the UPS Check whether the output of UPS or loads are short circuit Make sure the ...

Страница 30: ...ich the problem occurred 3 LCD LED display status Buzzer alarm status 4 Utility power condition load type and capacity environment temperature ventilation condition 5 The information battery capacity quantity of external battery pack if the UPS is C model 6 Other information for complete description of the problem w w w u p s d i r e c t c o m ...

Страница 31: ...orri 8 2 Storage If the batteries are stored in a temperate controlled area they should be charged every three months for 1 2 hours You should shorten the charging intervals to two months at locations subject to high temperatures 8 3 Battery Replacement If the battery service life has been exceeded the batteries must be replaced Battery replacement should be performed only by qualified personnel w...

Страница 32: ...W 3kVA 2 4kW Voltage 200 208 220 230 240 1 士2 VAC Frequency 50 60 1 0 2 Hz Battery mode Waveform Sinusoidal Derating to 90 when the output voltage is adjusted to 208VAC Derating to 80 when the output voltage is adjusted to 200VAC BATTERIES Model No B400 010 B B400 020 B B400 030 B Number and type 3 12V 7Ah 8 12V 7Ah 8 12V 7Ah 9 2 Operating Environment Ambient Temperature 0 o C to 45 o C Operating ...

Страница 33: ...10 B 5 14 B400 020 B 9 21 B400 030 B 5 15 9 4 Dimensions and weights Model No Dimensions W D H mm Net Weight kg B400 010 B 145 400 220 13 B400 010 C 145 400 220 7 B400 020 B 192 460 347 31 B400 020 C 192 460 347 13 B400 030 B 192 460 347 31 B400 030 C 192 460 347 13 w w w u p s d i r e c t c o m ...

Страница 34: ...B port and an intelligent slot are provided 10 1 USB The USB port is compliance with USB 1 1 protocol 10 2 RS232 Interface Option The following is the pin assignment and description of DB 9 connector Pin Description I O 2 TXD Output 3 RXD Input 5 GND Input w w w u p s d i r e c t c o m ...

Страница 35: ...ur local distributor for details The following is the pin assignment and description of DB 9 connector in AS400 card Pin Description I O Pin Description I O 1 UPS Fail Output 6 Bypass Output 2 Summary Alarm Output 7 Battery Low Output 3 GND Input 8 UPS ON Output 4 Remote Shutdown Input 9 Line Loss Output 5 Common Input DB 9 Interface of AS400 communication protocol w w w u p s d i r e c t c o m ...

Страница 36: ... same LAN regardless of distance from the UPSs Installation procedure 1 Go to the website http www borri co uk softwaredownload 2 Choose the operation system you need and follow the instruction described on the website to download the software 3 When downloading all required files from the internet enter the serial No 511C1 01220 0100 478DF2A to install the software When your computer restarts the...

Страница 37: ... 34 Appendix Rear panel Rear View of B400 010 B C Rear View of B400 020 B w w w u p s d i r e c t c o m ...

Страница 38: ...Back View of B400 020 C Back View of B400 030 B C w w w u p s d i r e c t c o m support upsdirect com 44 0 8456 445 002 www upsdirect com ...

Отзывы: