94
Operating manual for DGM Modular | DOC02389740-0006 | 2021-07 | V1.70 EN
Optional accessories
10.5 UL approval
10.5.1 UL Specification (English version)
Maximum Ambient Temperature:
Electronic
Adapter
Ambient
Suffix
INV MP(M) A IV01 PW03
ADP MA WDM
50 °C
-
INV MP(M) A IV01 PW04
ADP MA WDM
50 °C
-
INV MP(M) A IV01 PW05
ADP MA WDM
50 °C
-
INV MP(M) A IV01 PW06
ADP MA WDM
45 °C
-
INV MP(M) A IV01 PW46
ADP MA WDM
40 °C
-
INV MP(M) B IV01 PW07
ADP MB WDM
50 °C
GH4x, GH5x
INV MP(M) B IV01 PW08
ADP MB WDM
50 °C
GH4x, GH5x
INV MP(M) B IV01 PW09
ADP MB WDM
45 °C
GH4x, GH5x
INV MP(M) B IV01 PW49
ADP MB WDM
40 °C
GH4x, GH5x
INV MP(M) B IV01 PW07
ADP MB WDM
45 °C
Not GH4x, GH5x
INV MP(M) B IV01 PW08
ADP MB WDM
45 °C
Not GH4x, GH5x
INV MP(M) B IV01 PW09
ADP MB WDM
35 °C
Not GH4x, GH5x
INV MP(M) B IV01 PW49
ADP MB WDM
30 °C
Not GH4x, GH5x
INV MP(M) C IV01 PW10
ADP MC WDM
40 °C
-
INV MP(M) C IV01 PW11
ADP MC WDM
40 °C
-
INV MP(M) C IV01 PW51
ADP MC WDM
40 °C
-
INV MP(M) D IV01 PW12
ADP MD WDM
50 °C
-
INV MP(M) D IV01 PW13
ADP MD WDM
50 °C
-
INV MP(M) D IV01 PW14
ADP MD WDM
50 °C
-
INV MP(M) D IV01 PW15
ADP MD WDM
50 °C
-
INV MP(M) D IV01 PW55
ADP MD WDM
35 °C
-
Required Markings
To maintain the environmental integrity of the enclosure openings shall be closed by field-installed industrial conduit hubs
or closure plates at least suitable for enclosure type 1.
Short circuit current rating (SCCR)
“Suitable For Use On A Circuit Capable Of Delivering Not More Than 5000 rms Symmetrical Amperes, 480 Volts
Maximum When Protected by Class RK5 Class Fuses rated A:
INV MP A = max. 400 % motor current and not more than 15 A
INV MP B = max. 400 % motor current and not more than 35 A
INV MP C = max. 400 % motor current and not more than 35 A
INV MP D = max. 400 % motor current and not more than 100 A
CAUTION:
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with the Manufacturer Instructions, National Electrical Code and any additional local
codes.
CAUTION:
Use 75° C copper wires only.
CAUTION:
"Motor overtemperature sensing is not provided by the
drive”.
The Type of branch circuit protection devices used for BREAKDOWN OF COMPONENT TEST is Nonrenewable Cartridge
Fuse, Class _RK5.
As RK5 is the worst Case Type, any other Type can be used.
Содержание DGM MPM
Страница 1: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 1...
Страница 2: ...2 Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN...
Страница 3: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 3...
Страница 98: ......
Страница 102: ......
Страница 104: ......
Страница 105: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 101...
Страница 106: ......
Страница 107: ...Operating manual for DGM Modular DOC02389740 0006 2021 07 V1 70 EN 103...