AGL202 (3~:0.18 … 0.55 kW, 1~:0.09 … 0.25 kW, 230 V)
Type
230 V
Agile
202
-01
-02
-03
-05
Size
1
Output motor side
Selected Mains supply
1ph
3ph 1ph
3ph
1ph
3ph
1ph 3ph
Recommended
motor shaft power
P kW 0.09 0.18 0.12 0.25 0.18 0.37 0.25 0.55
Output current
I A
0.8 1.3 1.0 1.5 1.3 2.0 1.5 3.0
Long-term
overload current (60 s)
I A
1.2 2 1.5 2.25 1.95
3.0 2.25 4.5
Short-time
overload current (1 s)
I A
1.6 2.6 2.0 3 2.6 4.0 3.0 6.0
Switching frequency
f kHz
2, 4, 8, 16
Output, brake resistor
Minimum brake resistor
R
Ω
100
100 100
100
100
100
100 100
Recommended brake resis-
tor (385 V)
R
Ω
300
220 250
200
220
140
200 100
Input mains side
Rated current
I A
1.7 1.2 1.9 1.4 2.5 2.0 3.0 2.5
Maximum mains current
1)
I A
2.5 2.2 2.9 2.5 3.6 3.3 4.2 4.0
Fuses
I
A
6 6 6 6 6 6 6 6
Fuses UL type
I A
Bussmann FWP-10A14Fa
Mechanics
Dimensions
2)
HxWxD mm
200 x 60 x 170
Weight (approx.)
m kg
1.1
Degree of protection
- -
IP20 (EN60529)
Terminals
A
mm
2
Mains and motor
terminals:
0.2 … 4 (flexible with sleeve)
0.2 … 6 (rigid )
Terminals relay
output:
0.1 … 1.5
Installation
-
-
vertical
Interior fan
- -
no
Heat sink fan
- -
no
Ambient conditions
Power dissipation (2 kHz
switching frequency)
P W
12 12 19 19 29 29 42 42
1) According to DIN EN 61800-5-1.
2) Dimensions of the basic device.