Assembly
A
5
!
Danger!
Mains connection
,
,
,
Switch off power supply.
Dangerous voltage: The power terminals may carry dangerous voltages for some time even if the
power supply is switched off. Wait for some minutes before starting to work at the frequency inverter.
Make sure that the frequency inverter is de-energized.
,
Connect mains supply.
Note:
,
,
Do not carry out high voltage insulation tests on cables connected to the frequency inverter.
Use copper wire rated at 30 °C.
!
B
B
Only required for DC-link connections.
:
3
400 V
400 V
PE
L3
L2
L1
F1
F1
F1
0.5 Nm
AWG
mm
2
2.5
14
12
4
1.5
16
8
10
X1
GB
d
d
d > 100 mm
Installation spacing
Connection on IT mains configuration
For connection on IT mains configuration remove the IT-jumper.
Note:
The removement of the IT-jumper reduces the noise immunity. The noise
immunity can be improved by external filters.
L1, N
2 x 1.5
1 x 10
or
F1
3.0
5.5 7.5
kW
10
25 25
11
35
2.2
10
4.0
10
1.5
mm
2
2.5
4
A
PE
mm
2
2 x 2.5
1 x 10
2 x 4
1 x 10
0.25 ... 1.5
6
9.2
35