7 Troubleshooting
Yes
No
No
No
Yes
Yes
No
FAULT
CAUSE
REMEDY
Cooling air outlet too
high / High dew point
Overload protector
(SK/HT) tripped
Compressor noisy
Excessive
current
consumption
High pressure drop on
air side
High refrigerant
discharge
pressure
Condenser dirty
Ambient
temperature over
122°F (50°C)
Compressor
components
perished
Condenser dirty
Heat exchanger fouled
with debris
Fan pressure switch (PV)
calibration
error or
damaged
Clean
condenser
Reduce
temperature
Repair or
replace
compressor
Clean
condenser
Replace
pressure switch
Seek external as-
sistance
Ice formation on evapo-
rator (low evaporation
pressure)
By-pass air fl ow keep-
ing air inlet open. Open
condensate drain valve
manually.
Restart appliance checking
setting of expansion
valve.
Condenser
dirty
Fan does
not work
Replace
fan
Clean
condenser
Clean heat ex-
changer (blow com-
pressed air in opposite
direction to operating
air fl ow). Fit/renew
prefi lter
Fan does
not work
Compressor
winding insulation
partially perished
(compressor
too hot)
Repair
fan
Fan does not work
Excessive
thermal load (compressor
head too hot)
Reduce
compressed air
quantity or air
temperature
Repair
fan
Insuffi
cient
refrigerant: repair any
leaks and recharge the
circuit
Low current
consumption
Yes
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Содержание DS2 Series
Страница 101: ... 8 5 EXPLODED DRAWING 95 DS2 30 2 3 8 13 1 7 4 11 14 6 15 12 KA1 KT T01 ...
Страница 102: ... 8 6 DIMENSIONAL DRAWING DS 2 6 96 DS2 30 inches mm ...
Страница 103: ... 8 6 DIMENSIONAL DRAWING DS 9 12 97 DS2 30 inches mm ...
Страница 104: ... 8 6 DIMENSIONAL DRAWING DS 18 30 98 DS2 30 inches mm ...
Страница 105: ... 8 7 REFRIGERANT CIRCUIT 99 DS2 30 ...
Страница 106: ... 8 8 WIRING DIAGRAM DS 2 6 100 DS2 30 ...
Страница 107: ... 8 8 WIRING DIAGRAM DS 9 30 101 DS2 30 ...