Setting Parameters
5.2
Changing Individual Parameters
Page 20
BOGE
base
control for scroll compressors
5.2 Changing Individual Parameters
The required codes, description and step-by-step alteration of the individual
parameters are covered in this section.
Parameter Codes
Below is a table containing a list of codes that the user can use to change the
individual parameters:
Tab. 5.1: Codes and Editable Parameters
Compressor Servicing
Interval: Restart the
Counter / Change the
Start Value
This function is used to signal in advance the pending servicing of the com-
pressor. The hours until the next compressor servicing interval count down
from a start value (remaining hours). When the value reaches 0, the control
outputs a maintenance message. After servicing, the countdown counter must
be manually reset to the start value.
To
restart
and reset the countdown counter to the start value until the next
compressor servicing interval:
1. Unlock the code-protected parameters for the compressor servicing inter-
val using
code 111
.
The current start value for the countdown counter flashes on the seven-
segment display.
2.
Press the Enter key
.
The main display reappears on the control.
The servicing interval countdown counter has been reset to the start
value and restarted.
The start value for the remaining hours can be changed. To
reset / change
the start value of the countdown counter until the next compressor servicing
interval:
Code
Parameter function
Page
111
Setting the compressor servicing interval and restarting the counter
222
Setting the motor servicing interval and restarting the counter
360
Changing the target pressure values (switch-off / switch-on pressure)
(p
max
/ p
min
)
134
Activating / deactivating the Auto-Restart function
210
Activating / deactivating the external output release
CAUTION
Compressor Damage
If the servicing interval countdown counter is not restarted, urgently
required servicing work can be overlooked.
After all servicing work, the respective countdown counter must be
manually reset to the start value.