BOGE
base
control for scroll compressors
Page 33
Troubleshooting
6.4
Acknowledging Messages
Tab. 6.2: List / Meaning of Message Codes
Key to Table:
: Maintenance message
: Warning message
: Fault message
First
then
: First warning message, then fault message
* After servicing work, the respective countdown counter must be manually reset to the start value.
6.4 Acknowledging Messages
Once the cause of a message has been found and rectified, the message must
be acknowledged via the control unit to ensure that the compressor can be
operated again without restrictions. A message is acknowledged as follows:
1. The message view can be called up using the Info key
.
2. Press the Enter key
.
The main display reappears on the control.
The "Fault" indicator lamp goes out.
The "Ready" indicator lamp goes out.
The event has been acknowledged.
The compressor is operational again without restrictions
.
20
Continuous contact of an external control
–
Have the control settings in the master / slave parametri-
zation checked and if necessary corrected by authorized,
qualified personnel.
–
Have the master control checked for proper functioning
by BOGE Service personnel.
–
Check messages on the master control and if necessary
carry out fault rectification.
25
Incorrect calibration data
Have the control unit of the control checked and if necessary
replaced by BOGE Service personnel.
27
Control unit On key
does not open
Have the control unit of the control checked and if necessary
replaced by BOGE Service personnel.
29
Control unit Enter key
does not open
Have the control unit of the control checked and if necessary
replaced by BOGE Service personnel.
Type
Code
Message / Cause
Corrective Measures