Setting Parameters
5.2
Changing Individual Parameters
Page 26
BOGE
base
control for scroll compressors
Once "External output release" or "No external output release" has been
selected by calling up the corresponding display (Fig. 5.4 or 5.5):
3.
Press the Enter key
:
If the "External output release deactivated" display has been selected:
The main display appears again.
External output release is deactivated.
The compressed air generation is regulated exclusively by the inte-
grated compressor control.
If the "External output release activated" display has been selected:
The display for setting the first output release mode appears:
Fig. 5.6: External output release display – output release mode 1
Output Release Mode 1
If the external output release is to be activated, one of two different output
release modes must be selected.
The following applies in release output mode 1 in spite of the external output
release: If the actual network pressure falls below the set switch-on pressure
(p
min
) of the control, the control enables the compressor output independently
(without release from the master control) in order to prevent a complete loss
of pressure. At the same time,
message 18
(warning)
is output. If the switch-
off pressure (p
max
) is exceeded, the control switches off the compressor auto-
matically and outputs
message 20
(warning). This mode is recommended as
additional security against a complete loss of pressure (e.g. in hospitals).
4.
Press the Info key
.
The display for setting the second output release mode appears:
Fig. 5.7: External output release display – output release mode 2