2) Safety rules
•
Installation and maintenance of this equipment should only be carried
out by qualified personnel.
•
If the SIGMA is connected to the 230 V mains power supply, its installation
must comply with the European standard IEC 364 (NFC 15.100 for
France
).
PROTECTIONS :
•
110-230V version: the mains supply for this device must include a neutral
phase circuit breaker of maximum 6 A C curve, rapidly accessible upstream
from the supply.
•
24V DC version: the SELV 24 V power supply for this device must include a
protection of maximum 6 A.
•
36-72V DC version: the SELV 36-72 V power supply (according to NFC 15-
100) for this device must include a protection of maximum 6 A.
•
For the relay circuits, add protections with circuit beakers of maximum 4
A. Indicate on the labels the location of these protections.
•
The circuit breaker must be switched off during maintenance operation.
Refer to labels in the product.
•
All cables must be attached either to the wall (
wall-mounted version) or to
the frame of the cabinet (Rack version) before being connected to the various
terminals strips, to prevent any pulling on these terminal strips. In addition, the
wires of each terminal strips must be attached to each other to maintain the
various isolations if an initial fault occurs.
•
The time distribution cables
must not run alongside high power mains
cables (to avoid interference with communication between the SIGMA and the
clocks).
•
The SIGMA must be attached (to the wall or on its support) before being
switched on.