The tables below give information on the conformity of the units and the seasonal energy performance ratios with regard
to the reference regulation.
OMEGA SKY Xi
25.1
29.1
35.1
40.1
47.1
53.1
60.1
72.1
81.1
97.1
R513A
REGULATION 2016/2281
Pdesign
(1)
kW
252
304
361
404
459
525
590
718
810
940
Compliance 12/7
Compliance
(1)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ηsc
(1)
280%
290%
300%
307%
317%
316%
317%
316%
316%
288%
SEER
(1)
7,2
7,45
7,7
7,87
8,13
8,09
8,12
8,09
8,1
7,41
Compliance Tier 2 (2021)
(1)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Compliance SEPR
Compliance
(3)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
SEPR
(3)
8,28
8,56
8,66
8,74
8,82
9,00
9,04
9,1
9,11
9,16
R134a
REGULATION 2016/2281
Pdesign
(1)
kW
258
311
370
413
473
536
603
734
829
952
Compliance 12/7
Compliance
(1)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
ηsc
(1)
286%
296%
306%
315%
322%
323%
324%
323%
322%
291%
SEER
(1)
7,35
7,6
7,86
8,07
8,24
8,27
8,29
8,28
8,25
7,48
Compliance Tier 2 (2021)
(1)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Compliance SEPR
Compliance
(3)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
SEPR
(3)
8,44
8,73
8,83
8,93
9,03
9,23
9,28
9,29
9,27
8,86
Y = unit in compliance with Ecodesign at the indicated condition.
N = unit not in compliance with Ecodesign at the indicated condition: it can be installed only in non-EU countries.
(1) User-side heat exchanger water inlet/outlet temperature 12/7°C (low temperature application), with reference to regulation 2016/2281 and stand
-
ard EN 14825.
(3) User-side heat exchanger water inlet/outlet temperature 12/7°C, with reference to regulation 2016/2281 and norm EN 14825.
OMEGA SKY Xi HPW
40.1
47.1
53.1
60.1
72.1
81.1
R513A
REGULATION 2016/2281
Pdesign
(1)
kW
404
459
525
590
718
810
Compliance 12/7
Compliance
(1)
Y
Y
Y
Y
Y
Y
ηsc
(1)
307%
317%
316%
317%
316%
316%
SEER
(1)
7,87
8,13
8,09
8,12
8,09
8,1
Compliance Tier 2 (2021)
(1)
Y
Y
Y
Y
Y
Y
Compliance SEPR
Compliance
(3)
Y
Y
Y
Y
Y
Y
SEPR
(3)
8,74
8,82
9,00
9,04
9,1
9,11
R134a
REGULATION 2016/2281
Pdesign
(1)
kW
413
473
536
603
734
829
Compliance 12/7
Compliance
(1)
Y
Y
Y
Y
Y
Y
ηsc
(1)
315%
322%
323%
324%
323%
322%
SEER
(1)
8,07
8,24
8,27
8,29
8,28
8,25
Compliance Tier 2 (2021)
(1)
Y
Y
Y
Y
Y
Y
Compliance SEPR
Compliance
(3)
Y
Y
Y
Y
Y
Y
SEPR
(3)
8,93
9,03
9,23
9,28
9,29
9,27
Y = unit in compliance with Ecodesign at the indicated condition.
N = unit not in compliance with Ecodesign at the indicated condition: it can be installed only in non-EU countries.
(1) User-side heat exchanger water inlet/outlet temperature 12/7°C (low temperature application), with reference to regulation 2016/2281 and stand
-
ard EN 14825.
(3) User-side heat exchanger water inlet/outlet temperature 12/7°C, with reference to regulation 2016/2281 and norm EN 14825.