![BlueBox Omega Sky Xi Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/bluebox/omega-sky-xi/omega-sky-xi_technical-manual_2777379018.webp)
17
Other accessories
AG
Rubber anti-vibration mounts
These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on.
Accessory supplied loose.
AM
Spring anti-vibration mounts
These allow you to reduce the vibrations transmitted from the unit to the surface it is standing on.
Accessory supplied loose.
FLUS Flow switch
As an alternative to the differential pressure switch (standard flow sensor), it is possible to request the pad
-
dle flow switch as accessory. This detects when there is no water flow to the user-side exchanger and sends
a signal to the control of the unit that will stop the compressors to prevent damage to the exchangers.The
flow switch is supplied loose (installation by the customer) and replaces the water differential pressure switch
(standard).
GABB Packaging in wooden crate
The unit is protected by a made-to-measure wooden crate. The accessory is mandatory if shipping by contain
-
er is required.
KFW
Water filter kit
To protect the elements of the hydraulic circuit (in particular, the exchangers), there are Y filters that can stop
and settle the particles that are normally present in the water flow and would otherwise settle in the more
delicate parts of the hydraulic circuit and damage its heat exchange capacity.
The kit involves the supply of a filter for each exchanger present in the machine.
Installation of the water filter is mandatory even when it is not supplied as an accessory.
Accessory supplied loose.
Depending on the version of the unit, user side and source side filters are supplied, and for DC version units,
heat recovery side filters are also supplied.