3.3.3
E3 / Evaporator sensor temperature is over 60
℃
(140
℉
)
3.3.4
E4 / Water is not drained during full storage
Evaporator temperature
sensor
is over 60℃(140℉)
Are the environmental
conditions
within
specification?
No
Change
installation place
Yes
센서가
실제온도
와
같은가
?
No
Replace sensor
Yes
Insulate evaporator
sensor
Water is not sufficiently drained within set drainage time
[default: 480 seconds] when the ice storage bin is full.
Is the water
drained?
No
Connect the
drainage line
Is the drainage line inside of the
ice machine properly connected?
No
Yes
Is the water drained
while test mode?
Replace parts
related to drainage
No
Yes
Replace main
PCB
Yes