4.3.1  

Manual Adjust (manual speed adjust)

Used to manually control the speed of pump. Set % (percent) Motor Speed in 
this menu.

Press SELECT RUN MODE button until 

Manual Speed Adjust 

is displayed in 

the top line of the display. 

To configure the pump output speed, navigate to 

Manual Speed Adjust

 menu 

by using the short-cut method described above, or by pressing MENU button, 
then selecting Input Setup, Input Modes, and then 

Manual Adjust

.

Press UP or DOWN arrow to scroll through 0 - 9 on selected digit.

Press RIGHT arrow to scroll over to next digit to right. If you pass your desired 
digit, you can easily scroll back by continuously pressing RIGHT button.

Press ENTER to save changes.

If you used the short-cut to enter Manual Speed Adjust setup, press and hold 
the Select Run Mode button until the Run Mode screen is displayed.

If you used the Menu button to navigate to the Manual Speed Adjust setup, you 
must navigate back out of the menu structure. To do this you must select <-Esc 
at the bottom of every screen menu until you see the Run Mode screen 
displayed.

Tip!

  The 

Manual Speed Adjust 

mode can be combined with 

Contact Input

 

feature to allow for remote Start and Stop of pump. Can be used with PLC, foot 
pedal, push button, or other external controls.

Tip!

Run Mode

(operating Input Mode)

- Speed Adjust

   Input Pump Speed:

Set % motor speed.
Press ENTER to set.

00.0%

0

MODE button also serves as a 
shortcut button.

Press and Hold

 MODE button to 

enter the programming menu for the 
current Run Mode. After programming 
the Run Mode, press ENTER to save 
changes. 

Press and Hold

 MODE 

button to exit the program menu back 
to the current Run Mode of the pump.

Press

 START button to start the 

pump with the new settings applied.

In Manual Speed Adjust 
mode, you can view the 
pump output by pressing 
RIGHT arrow. RIGHT 
arrow is a convenient way 
to scroll through multiple 
read-only screens during 
normal pump operation.

Tip!

Manual Speed Adjust

GAL/DAY

228

Å

É

ÄÈ

Displays motor run status

4.3  Input Setup (operating mode configuration)

4.3.2  

4 - 20 mA Input

Used to remotely control the pump with an incoming 4-20 mA signal.

Default settings:  

4 mA = 0% motor speed

 

 

 

 

 

20 mA = 100% motor speed

Press MODE button until 

4 - 20 mA Input 

is displayed in the top line of the 

display. 

To configure the pump, navigate to 

4 - 20 mA Input

 menu by using the short-cut 

method described at the beginning of section, or by pressing MENU button, then 
selecting Input Setup, Input Modes, and then 

4 - 20 mA Input

Four points on the slope must be defined; 1) a low mA value, 2) an output rate at 
the low mA value, 3) a high mA value, and 4) an output rate at the high mA 
value. 

To input mA values, press the RIGHT ARROW to select the digit to change, 
press UP or DOWN arrow to scroll through 0 - 9 on selected digit. Press enter to 
save changes and move to the next input screen.

To input flow rate values, press the RIGHT ARROW to select the user defined 
flow rate unit of measure, motor RPM, or %Speed values. Press UP or DOWN 
arrow to increase or decrease the value. Press and hold the arrow to increase or 
decrease progressively faster. Press enter to save changes and move to the 
next input screen.

Continue this process until all four screens have been configured.

If you used short-cut to enter 4-20 mA input setup, press and hold the Mode button until the Run Mode screen is 
displayed.

If you used Menu button to navigate to 4-20 mA input setup, you must navigate back out of menu structure. To do 
this you must select <-Esc at bottom of every screen menu until you see Run Mode screen displayed.

Note: The pump is designed to fail safe. If the input signal drops below 3.0 mA,  the pump assumes a lost 
signal and the motor speed is set to 0 RPM. 

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

Motor Speed (%)

Milliamp input (mA)

from external source

4 mA = 0% Pump Output

20 mA = 100% Pump Output

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 100% Pump Output

20 mA = 0% Pump Output

Example 3

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 20% Pump Output

16 mA = 43.8% Pump Output

0%

Output

Pump

Motor Speed (%)

Pump

Motor Speed (%)

100%

Output

100%

Output

0%

Output

43.8%

Output

20%

Output

Milliamp input (mA)

from external source

Milliamp input (mA)

from external source

- 4-20 mA Input

Flow @ Min Signal:

Input Flow Rate
                          

GPH

00.0

0

- 4-20 mA Input

Min mA Signal:

Input Min. mA signal Input.

4.00

0

- 4-20 mA Input

Max mA Signal:

Input Max mA Signal

0.00

2

Press ENTER to set.

Press ENTER to set.

- 4-20 mA Input

Flow @ Max Signal:

Input Flow Rate 
                         

GPH

00.0

0

MODE

Page 16

Page 17

®

CHEM-FEED  MD3

®

CHEM-FEED  MD3

Содержание CHEM-FEED MD3 Series

Страница 1: ...Diaphragm Metering Pump Series MD3 CHEM FEED...

Страница 2: ...3 1 Manual Adjust manual speed adjust 16 4 3 2 4 20 mA Input 17 4 3 3 0 10 VDC Input 18 4 3 4 Frequency Input Hz 19 4 3 5 Pulse Batch low speed batch 20 4 3 6 Manual Cycle Adjust repeating cycle time...

Страница 3: ...m Model Number Matrix READ THE INSTRUCTION MANUAL PRIOR TO INSTALLATION AND USE 1 714 893 8529 sales blue white com customerservice blue white com 5300 Business Drive Huntington Beach CA 92649 Page 3...

Страница 4: ...115V60Hz NEMA 5 15 USA 230V60Hz NEMA 6 15 USA 220V50Hz CEE 7 VII EU 240V50Hz AS 3112 Australia New Zealand Pump Head Assembly Pump Head PVDF Manifold PVDF Adapter Connections PVDF Valve Cartridges PVD...

Страница 5: ...ite s output Flow Verification Sensor FVS system Includes stainless steel extended mounting brackets Lifts pump 4 1 2 11 43 cm for easy access in hard to reach areas Enclosure Rating NEMA 4X Construct...

Страница 6: ...n check valve at discharge side of pump to prevent system fluid from flowing back through pump during pump maintenance A pressure relief valve is recommended at discharge of pump Bolt pump to a stable...

Страница 7: ...0cm 4 00in 10 15cm n Made out of tough Stainless Steel n Provides a stable mounting surface Stainless Steel extended brackets allow the pump to be securely mounted to most any surface floor shelf or s...

Страница 8: ...d and sealed Never strap control input output cables and power cables together Power Interruption This pump has a user programmable auto restart feature which will either restore the pump to the opera...

Страница 9: ...AMP MAX AT 125 VOLT AC 0 8 AMP MAX AT 30 VOLT DC 5A SLOW BLOW 20 X 5MM 1 2 3 T1 PULSE GND 4 20 1 2 3 T1 PULSE GND 4 20 0 10 15VDC 1 2 T2 0 1000 HZ MAX NEGATIVE POSITIVE POSITIVE NEGATIVE NO VOLTAGE 96...

Страница 10: ...elect menu items increase menu values by one and increase pump output in Manual Speed Adjust mode Press and hold to increase values progressively faster Press and release to stop the pump Press and re...

Страница 11: ...e While making a selection where only one choice is allowed you will see a radio button Radio button example In a screen where you are making changes you will see the word Done located at the bottom o...

Страница 12: ...e menu structure and enter the run mode Configuration Display Language Set Password Display Rate Esc Reset to Default Display Language English Spanish German Done French Display Language Configuration...

Страница 13: ...gled through Speed RPM and your selected Display Rate by pressing the right arrow button Press MENU button to enter the menu structure Select Configuration and Press ENTER button Select Display Rate a...

Страница 14: ...wrate Flowrate ML min Press ENTER to set 0000 0 1 Contact Input Close Stop Pump Open Stop Pump Input Time Delay OFF 000 Range 1 255 sec Disable 00 0 Input Setup 4 20 mA Input Frequency Input Pulse Inp...

Страница 15: ...rate Input Modes Contact Input Set FVS Esc Hidden Remote Local Set DFD Set Rev Alarm Max Flowrate Input Max Flowrate Flowrate ML min Press ENTER to set 0000 0 1 To calculate the Max Flowrate To determ...

Страница 16: ...ack out of the menu structure To do this you must select Esc at the bottom of every screen menu until you see the Run Mode screen displayed Tip The Manual Speed Adjust mode can be combined with Contac...

Страница 17: ...process until all four screens have been configured If you used short cut to enter 4 20 mA input setup press and hold the Mode button until the Run Mode screen is displayed If you used Menu button to...

Страница 18: ...top line of the display To configure the pump navigate to 0 10 VDC Input menu by using the short cut method described at the beginning of the section or by pressing MENU button then selecting Input Se...

Страница 19: ...select the digit to change press UP or DOWN arrow to scroll through 0 9 on selected digit Press enter to save changes and move to the next input screen To input flow rate values press the RIGHT ARROW...

Страница 20: ...k by continuously pressing the RIGHT button Press ENTER to save the changes Continue this process until all three screens have been configured If you used the short cut to enter Pulse Batch setup then...

Страница 21: ...onfigured If you used the short cut to enter Manual Cycle Adjustment setup press and hold Mode button until Run Mode screen is displayed If you used the Menu button to navigate to Cycle Adjustment set...

Страница 22: ...xt digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until two screens have been...

Страница 23: ...arrow to scroll over to next digit to the right If you pass your desired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process un...

Страница 24: ...esired digit you can easily scroll back by continuously pressing RIGHT button Press ENTER to save the changes Continue this process until all four screens have been configured If you used the short cu...

Страница 25: ...gering due to flickering high speed electrical switches a trigger delay time can be configured to delay the pump command The delay time unit of measure is seconds A two second delay time is recommende...

Страница 26: ...n discharge side of MD3 pump Wiring for sensor can be connected directly to a MD3 pump Pump will stop pumping if sensor detects no flow A relay will then close allowing for remote alarm indication or...

Страница 27: ...an 430 microsiemens will not be detected This system is capable of detecting presence of a large number of chemicals including Sodium Hypochlorite Chlorine Hydrochloric muriatic Acid Sodium Hydroxide...

Страница 28: ...etting section 4 4 is switched to disabled while LOCAL ONLY is selected This menu setting will return to the previous setting when REMOTE ONLY or DISABLED is selected Input Setup Input Modes Contact I...

Страница 29: ...Stop Frequency Mode Cycle Timer Mode Dispensing Mode Manual Dosing Prop Dosing 0 10 VDC Mode Pulse Mode Disable FVS DFD Pump Run Stop 4 20mA Mode Manual Mode Frequency Mode Cycle Timer Mode Dispensing...

Страница 30: ...0 Pump Output 4 mA 100 Pump Output 20 mA Signal Output Frequency Output Disable Done 4 20 mA Output Default 4 20 mA output settings shown Signal Output Disable Done 4 20 mA Output Default Frequency H...

Страница 31: ...r does not assume responsibility for damage to pump that has been caused by chemical attack 6 2 Cleaning Pump Pump will require occasional cleaning especially Injection fitting Footvalve Strainer and...

Страница 32: ...7 0 Exploded view and parts list 1 2 4 6 8 7 10 22 9 15 14 3 13 11 3 12 Page 32 CHEM FEED MD3...

Страница 33: ...001 505 MANIFOLD WITH FLANGE AND UNION NUT PLUG WITH O RING EP 6 90002 350 DRIVE HEAD INSERT 2 7 72000 583 KIT DIAPHRAGM PVDF MD3 2 8 70001 345 CARTRIDGE VALVE TFE P 8 70001 346 CARTRIDGE VALVE EP 9 9...

Страница 34: ...32 151 303 751 1508 2252 3041 RPM 1 3 10 19 48 95 142 190 GPH 0 5 2 4 4 8 11 9 23 9 35 7 48 2 Feed Rate at 90 PSIg ML MIN 25 145 278 694 1388 2107 2391 RPM 1 3 10 19 48 95 142 190 GPH 0 4 2 3 4 4 11 0...

Страница 35: ...Page intentionally left blank Page 35 CHEM FEED MD3...

Страница 36: ...Page intentionally left blank Page 36 CHEM FEED MD3...

Страница 37: ...Page intentionally left blank Page 37 CHEM FEED MD3...

Страница 38: ...iption of the problem and proof of purchase Prepay all shipping and insurance cost COD shipments will not be accepted Damage caused by improper packaging is the responsibility of the sender When In Wa...

Страница 39: ...ia New Zealand 9 230V 50HZ power cord BS 1363 A plug United Kingdom X No Power Cord Elastomer Material O Rings V TFE P E EP Miscellaneous Options leave blank for standard model A Hastelloy C check val...

Страница 40: ...ramework available to them for the return recycle recovery of WEEE and minimize any potential effects of EEE on the environment and human health due to the presence of hazardous substances The WEEE ma...

Отзывы: