![Blue-White CHEM-FEED CFWS Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/blue-white/chem-feed-cfws-series/chem-feed-cfws-series_operating-manual_2777001012.webp)
Connections:
Connect chemical solution into Inlet. (V-1)
Connect chemical treated system to outlet. (V-13)
To Pump chemical solution into system.
Open ball valve V-1.
Open ball
valve V-3, or V-4, depending on which pump is being used.
Close ball valve V-2, V-11, and V-12.
Open ball valve V-5 or V-6, depending on your system design.
Open ball valve V-7, V-8, V-9, V-10 depending on your system design.
Open ball valve V-13 to inject chemical solution into your system.
Start pump(s).
To calibrate pump(s) / system.
Open ball valve V-1.
Open ball valve V-3 or V-4, depending on which pump is being calibrated.
Open ball valve V-5 or V-6, depending on which pump is being calibrated.
Close ball valve V-2, V-11, and V-13.
Open ball valve V-12. This open valve will direct chemical into calibration cylinder.
Start pump and run until calibration cylinder is filled to top calibration line. Do not leave pump unattended during
this operation!
Stop pump once calibration cylinder is filled.
Close ball valves V-1 and V-12.
Open ball valve V-2 and V-13 to inject chemical solution into your system.
Note the chemical solution level in the calibration cylinder.
To calibrate pump at maximum speed into your system, Press the prime button on pump. The prime mode runs the
®
pump at maximum speed for 60 seconds (1 minute) on all Blue-White pumps.
To calibrate pump at your desired feed rate, you must pre-program your pump speed before running this routine.
Please refer to the instruction manual for your pump to adjust feed rate and additional calibration instructions.
Repeat process to ensure accuracy of calibration.
8.1
How To Operate the Chem-Feed® Duplex Skid System
Page 12
®
CHEM-FEED CFWS
V-2
Chemical Inlet
Chemical Outlet
U-1
S-1
Ms6
BPV-1
PD-2
PSH-1
G-1
PD-1
PRV-1
PRV-2
S-2
U-2
U-6
U-3
U-4
CV-1
CV-2
U-5
U-8
U-7
U-9
CC-1
V-3
V-4
V-5
V-11
V-7
V-8
V-9
V-10
V-13
V-12
V-6
V-1
CHEM-FEED
®
Simplex Wall Skid System - Municipal
CFWS-1
Single pump system - single chemical / single outlet, PE structure
Inlet/Outlet
A
Single Inlet / Single Outlet
X
None, Skid Panel Only
Piping/Unions
A
PVC
C
PVDF
B
CPVC
D
CHEM PROLINE®
Seals
V
FKM
E
EPDM
Tubing Connections
A
1/2” ID PVC Braided
C
1/4” ID PE
B
1/2” ID PTFE
D
1/4” ID PTFE
Calibration Column
A
128 GPH (4000 ml) PVC
F
3 GPH (100 ml) PVC
B
64 GPH (2000 ml) PVC
P
32GPH (1000 ml) Glass
C
32 GPH (1000 ml) PVC
Q
16 GPH (500 ml) Glass
D
16 GPH (500 ml) PVC
R
8 GPH (250 ml) Glass
E
8 GPH (250 ml) PVC
S
3 GPH (100 ml) Glass
Pulsation Dampener
P
10 cubic in
X
Not Included
Back Pressure Valve
B
Included
X
Not Included
Pressure Gauge w/Guard
A
200 PSI
B
100 PSI
C
30 PSI
Pressure Switch w/Guard
S
Included
X
Not Included
Flow Meter w/Strainer
A
10-5000 mL/min
B
100-10000 mL/min
X
Not Included
CFWS-1
M
A
A
V
A
A
P
B
A
S
A
X
X
Sample Model Number
Model Number Matrix
CFWS-1-M
NOTES:
When ordering pumps for skids, pump head orientation is standard LEFT facing only. Terminal Boxes quoted and mounted separatel y.
All skids are pressure tested prior to shipment. Pumps are puchased and shipped separately.
Page 13
®
CHEM-FEED CFWS
®
9.0
Chem-Feed Skid System Matrix