BATTERY AND PV WIRING 

 

 

A desirable installation will produce a total system wiring voltage drop of 3% or less. The lengths shown in Table 2 are one way from the PV modules to the 

battery with the 2512 located along the path. Wire length can be increased inversely proportional to actual current. If current was reduced by ½, wire lengths could 
be doubled and still provide the same 3% voltage drop. 

 

MAXIMUM CONDUCTOR PAIR LENGTH   

––

   3% VOLTAGE DROP 

 

WIRE GAUGE 

AWG 

12 VOLT SYSTEM @20AMPS 

FEET / METERS 

12 AWG 

6.4 / 1.9 

10 AWG 

10.2 / 3.1 

8 AWG 

16.2 / 4.9 

6 AWG 

25.7 / 7.8 

4 AWG 

40.8 / 12.5 

 

TABLE 2 

 

¾

 

CAUTION:

 Battery, PV and Auxiliary Output terminal block accept #20

10 AWG wire and are to be tightened to 9 in-lb (1 

nm). IPN Network and Temperature Sensor compression terminals accept #24

14 AWG wire and are to be tightened to 2.1 in-

lb (0.24 nm).  

 

¾

 

CAUTION:

  DO  NOT  connect  Bat––  and  PV––  together  outside  of  the  unit  or  improper  operation  will  result.  Bat––  and  PV–– 

connect together internally. 

 

SETUP AND WIRING DIAGRAM 

 

 

 

FIGURE 3 

 

AUXILIARY OUTPUT  

(Omitted on SB2512i)

 

 

 

The auxiliary output can serve one of three functions; a 2 amp auxiliary battery charger, a 25 amp load controller with Low Voltage Disconnect (LVD), or a 

25 amp variable Dusk-to-Dawn lighting load controller. The Charge/Load function is selected by DIP switch #3 shown in Figure 3. The IPN-ProRemote is required 
to adjust LVD thresholds or enable Dusk-to-Dawn lighting control. Auxiliary outputs in a multi-controller system will function normally, but only the auxiliary output in 
the master can be configured or monitored using the IPN-ProRemote. The auxiliary output Load Indicator will illuminate whenever the auxiliary output is ON. 

 

¾

 

CAUTION:

 The auxiliary output cannot perform both auxiliary battery charge and load control functions at the same time. Do not 

connect to the 25amp Load terminal for auxiliary battery charge. 

 

 

 

 

 

Содержание Solar Boost 2512i

Страница 1: ...IC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODELS SB2512i and SB2512iX SAVE THESE INSTRUCTIONS COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS 6 111 391 x 6 204 645 Blue Sky Energy Inc 2011 430 0021 E ...

Страница 2: ...LLATION 5 Electrostatic Handling Precautions 6 Selecting PV Modules 6 As Shipped Factory Default Settings 6 Equalize Enable 6 Battery Temperature Sensor 6 Battery and PV Wiring 7 Auxiliary Output 10 Auxiliary Battery Charge 8 Load Controller 8 Dusk to Dawn Lighting Control 8 Installing a Multi Controller System 8 Multi Controller Wiring And Setup 8 IPN Network Address 9 Mounting 9 TROUBLESHOOTING ...

Страница 3: ...battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION a This unit is designed to charge 12V 6 cell flooded or sealed type lead acid chemistry batteries within the range of 20 to 10 000 amp hours Follow battery manufacturer...

Страница 4: ...oller coordination x Auxiliary Output for load lighting control or auxiliary battery charge PART NUMBERS AND OPTIONS x SB2512i Basic Solar Boost 2512i charge controller x SB2512iX Full featured Solar Boost 2512iX charge controller x IPNPRO IPN ProRemote display battery monitor x IPNPRO S IPN ProRemote with required 500A 50mV current shunt x CS 500 500A 50mV current shunt x IPNREM IPN Remote displa...

Страница 5: ...at charge voltage setting to No Float using the IPN ProRemote Refer to the IPN ProRemote operators manual FRONT PANEL INDICATORS FIGURE 1 EQUALIZATION Omitted on SB2512i WARNING Not all batteries can be safely equalized Equalization should be performed only on vented liquid electrolyte lead acid batteries Always follow battery manufacturers recommendations pertaining to equalization Equalization a...

Страница 6: ...e about 10 20 increase Charge current increase can go to zero in hot temperatures whereas charge current increase can easily exceed 30 with a discharged battery and freezing temperatures For a more complete MPPT description see www blueskyenergyinc com PANEL TEMPERATURE AND OUTPUT POWER Internal power control devices use the front panel as a heatsink It is normal for the front panel to become quit...

Страница 7: ...ance Select PV modules that do not exceed the maximum ratings shown below and preferably produce at least 3A of IMP per 100 amp hours of battery capacity Recommended range of VMP at STC Maximum PV Power STC Maximum PV Isc STC Maximum PV VOC STC Nominal 12V PV 340W 20A 28 0V 16 5 18 5V AS SHIPPED FACTORY DEFAULT SETTINGS The 2512 contains various user configurable settings all of which are preconfi...

Страница 8: ...2 1 in lb 0 24 nm CAUTION DO NOT connect Bat and PV together outside of the unit or improper operation will result Bat and PV connect together internally SETUP AND WIRING DIAGRAM FIGURE 3 AUXILIARY OUTPUT Omitted on SB2512i The auxiliary output can serve one of three functions a 2 amp auxiliary battery charger a 25 amp load controller with Low Voltage Disconnect LVD or a 25 amp variable Dusk to Da...

Страница 9: ...n lighting control is enabled the Load output is controlled by both the normal load control function and the lighting control function such that whichever function wants the Load output OFF prevails Dusk or night time begins when the charge control system turns OFF which occurs when PV module current drops below 50mA at battery voltage Dawn or day time begins when the charge control system turns O...

Страница 10: ...ESS MASTER SLAVES DIP SWITCH 0 1 2 3 4 5 6 7 JUMPER A2 NO NO NO NO YES YES YES YES 1 A1 OFF OFF ON ON OFF OFF ON ON 2 A0 OFF ON OFF ON OFF ON OFF ON MOUNTING CAUTION Mount the 2512 vertically to promote air flow and do not enclose in a confined space The 2512 is not watertight and must be protected from rain snow and excessive moisture Take care not to place mounting screws under large brown capac...

Страница 11: ...d battery voltage is high Output during MPPT operation is constant power higher battery voltage reduces charge current increase VMP and available power decrease with increasing PV cell temperature Cooler PV s will produce greater boost It is normal for boost to decrease as PV temperature rises Replace use as is or use different controller for different PV modules Auxiliary battery not being chargi...

Страница 12: ...nt process With IPN ProRemote which may be used as specifications are subject to change without prior notice a setup tool only or permanently installed FIVE YEAR LIMITED WARRANTY Blue Sky Energy Inc hereinafter BSE hereby warrants to the original consumer purchaser that the product or any part thereof shall be free from defects due to defective workmanship or materials for a period of five 5 years...

Отзывы: