  WARNING: 

If  charge  parameter  settings  are  changed,  confirm  that  the  new  settings  comply  with  the  battery 

manufacturers recommendations. DO NOT enable equalization for sealed lead-acid batteries such as GEL and AGM. 

 

As Shipped Factory Default Settings 

  Charge mode  .......................................  3-stage 

  Equalize enable  ................................................ .. Off (disabled)  

  Absorption voltage  .............................  14.4V 

  Equalize time  ................................................... .. 2.0 hours 

  Absorption time  ..................................  2.0 hours 

  Equalize voltage  ............................................... .. 15.2V 

  Float voltage  ........................................  13.2V 

  Auto equalize days  ........................................... .. 30 days 

  Maximum setpoint voltage limit  .........  15.5V 

  Temperature compensation factor  ................. .. 

5.00mV/

C/cell 

  Auxiliary output mode  .......................  Aux Bat Charge 

  PostDusk lighting timer  .................................. .. Off (disabled) 

  LVD on voltage  ...................................  12.6V 

  PreDawn lighting timer ................................... .. Off (disabled) 

  LVD off voltage  ...................................  11.5V 

  Middle of the night lighting control dimming... 0% 

 

Restoring As Shipped Factory Default Settings 

1.

 

Remove both PV and battery power. 

   

4. 

After at least 5 seconds, release Setup. 

2.

 

Apply battery power while pressing & holding the Setup push-button.  5. 

Confirm display resumes normal operation. 

3.

 

Following display self-test, confirm display shows software revision  

6. 

The 3000i is now set to as shipped factory defaults. 

  (e.g., 

r1.4

) & Charge Status LED’s remain on while Setup is held.

 

Changing Charge And Load Control Settings 

3000i  charge  parameter  settings may be viewed or changed  at any time using a combination of  the Setup and Display Select push-buttons. 
There are two modes of setup operation, 

Viewing

 a setting and 

Changing

 a setting. Basic operation is to go from Normal Operation to Viewing 

Mode, Viewing Mode to Changing Mode, and then from Changing mode back to Viewing mode, and Viewing Mode back to Normal Operation. 
All settings are stored in Flash memory and are retained if power is lost. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

CHARGE AND LOAD CONTROL SETTINGS 

 

Parameter viewing mode 

toggles between setting text 

and value of that setting 

Setting Range 

Setting 

Steps 

Description 

Setting Text 

Default Setting 

AbS 

14.4 

12.0V 

 17.0V 

0.1V 

Absorption charge voltage 

Abt 

2.0 

  0.0 

 10.0 hrs 

0.5 hrs 

Absorption charge time 

FLt 

13.2 

12.0V 

 17.0V 

0.1V 

Float charge voltage 

Set to 

oFF

 (one step below 12.0) for 2-stage charge 

EqU 

15.2 

12.0V 

 17.0V 

0.1V 

Equalize charge voltage 

Eqt 

2.0 

  0.5 

 10.0 hrs 

0.5 hrs 

Equalize charge time 

Normal Display Operation 

Parameter Viewing mode  

Parameter Changing Mode 

Viewing a setting 
To enter the Viewing Mode press Setup 5 seconds and release when 

AbS

 appears in the display. The first parameter 

to be shown is the 

Absorption Charge Voltage

 setting. The display will alternate between 

AbS

 and 

14.4

 to show the 

present 

Absorption Charge Voltage

 setting is 14.4V.  

 
A brief press of Setup within 5 seconds will move to the next setting shown in Table 2, 

Absorption Charge Time

 

where the display will now alternate between 

Abt

 and 

2.0

 to show the present 

Absorption Charge Time

  setting is 

2.0 hours. Remaining settings may be viewed by repeatedly pressing Setup to move to the desired setting. To exit 
Viewing Mode and return to normal operation, do not press Setup for 5 seconds. 

Changing a setting 
To enter the Changing Mode, first enter the Viewing Mode for the setting to be changed. While in Viewing Mode 
for that setting, press Setup 5 seconds to enter the Changing Mode for that setting. The present setting value will 
begin blinking rapidly indicating that you have entered the parameter changing mode for that setting. Use Display 
Select to scroll through the available values until the desired value is reached. With the desired new value blinking 
in the display press Setup 5 seconds to save the new setting. Once the new setting is saved the display will revert 
back to the Viewing Mode showing the new saved value for that setting.  
 
If neither Setup or Display Select is pressed within 5 seconds while in the Changing Mode, the change request is 
abandoned and the display reverts back to Viewing Mode without changing the setting. 

Содержание SB3000i

Страница 1: ...RE OF THE FOLLOWING US PATENTS 6 111 391 6 204 645 Blue Sky Energy Inc 2017 430 0034 C FCC CFR 47 Part 15 Subpart B This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operations CONFORMS TO EN 6...

Страница 2: ...ped Factory Default Settings 7 Changing Charge And Load Control Settings 7 Selecting PV Modules 8 Mounting 8 Battery and PV Wiring 9 Optional Battery Temperature Sensor 9 Auxiliary Output 10 Auxiliary Battery Charge 10 Load Controller 10 Dusk To Dawn Lighting Control 11 Battery PV Power Connect Disconnect Order 11 Connecting The Battery 11 Connecting PV Modules 11 Installing A Multi Controller Sys...

Страница 3: ...cid battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION a This unit is designed to charge 12 volt 6 cell flooded or sealed type lead acid chemistry batteries within the range of 20 to 2 000 amp hours Follow battery manuf...

Страница 4: ... to prevent unwanted current drain There is a 5 second turn on delay and a 45 second turn off delay The 3000i operates on battery power not PV power Insure that voltage on the battery terminals of the 3000i is always the same as actual battery voltage within a few 10ths of a volt and greater than 9 volts for proper operation Note that the front panel serves as a heatsink for power control devices ...

Страница 5: ...end to be higher under light load and lower under a heavier load Do not think of these voltage values as absolutes but rather as a broad brush indication of approximate battery charge level Voltage at a particular state of charge will vary with battery size age construction temperature and with the level of charge or discharge current Most battery manufacturers recommend not discharging below abou...

Страница 6: ...nt PV over current protection and not a normal mode of operation If the 3000i enters 30 amp or 22 amp current limit on a regular basis it is possible that excessive PV power is connected Confirm that the PV modules do not exceed ratings shown in the Selecting PV Modules section OPTIONAL TEMPERATURE COMPENSATION The charge voltage required by batteries changes with battery temperature Temperature c...

Страница 7: ...s use the front panel as a heatsink It is normal for the front panel to become quite warm to the touch when the 3000i is operating normally Front panel heating will be the greatest when the 3000i is processing either very high power or very low power When mounted to a vertical surface with good ventilation the 3000i can deliver full output in an ambient temperature of up to 45 C 113 F If an over t...

Страница 8: ...nd value of that setting Setting Range Setting Steps Description Setting Text Default Setting AbS 14 4 12 0V 17 0V 0 1V Absorption charge voltage Abt 2 0 0 0 10 0 hrs 0 5 hrs Absorption charge time FLt 13 2 12 0V 17 0V 0 1V Float charge voltage Set to oFF one step below 12 0 for 2 stage charge EqU 15 2 12 0V 17 0V 0 1V Equalize charge voltage Eqt 2 0 0 5 10 0 hrs 0 5 hrs Equalize charge time Norma...

Страница 9: ... boost performance When multiple controllers are used on the IPN Network each controller independently MPPT s their modules to their best Do not mix 36 cell and 60 cell modules on the same controller Select PV modules that do not exceed the maximum ratings shown below and preferably produce IMP of at least 3 5 amps 2 amps with 60 cell modules per 100 amp hours of battery capacity Voltage current a...

Страница 10: ...e two wire sizes larger than shown e g 8awg rather than 12awg for the wire section between the 3000i and the battery MAXIMUM CONDUCTOR PAIR LENGTH 3 VOLTAGE DROP WIRE GAUGE AWG 60 CELL MODULES 11 8AMP INPUT FEET METERS 36 CELL MODULES 24AMPS INPUT FEET METERS 12 AWG 17 9 5 5 5 3 1 6 10 AWG 28 5 8 7 8 5 2 6 8 AWG 45 3 13 8 13 5 4 1 6 AWG 71 2 21 7 21 4 6 5 4 AWG 114 1 34 8 34 0 10 4 TABLE 3 CAUTION...

Страница 11: ...ted or not CAUTION The auxiliary output CANNOT perform both auxiliary battery charge and load lighting functions at the same time DO NOT use the 20 amp Load terminal for auxiliary battery charge or the 3000i may be damaged in a manner that voids the warranty For clarity Figure 5 only shows additional wiring required for auxiliary output use and assumes basic system wiring shown in Figure 4 is comp...

Страница 12: ...timer If both timers are set to DISABLED factory default the lighting control feature is disabled If either the Post Dusk PSt or Pre Dawn PrE timers are set to a time value the lighting control feature is enabled When lighting control is enabled the Load output is controlled by both the normal LVD control function and the lighting control function such that whichever function wants the Load output...

Страница 13: ...n and the front panel may get hot quickly Should this occur immediately remove PV power and correct the fault INSTALLING A MULTI CONTROLLER SYSTEM USING THE IPN NETWORK The 3000i may also serve as an IPN Network Master controlling up to 7 remote IPN Network compatible Slaves Any Blue Sky Energy charge controller capable of operating as an IPN Network Slave may be used and as of this writing includ...

Страница 14: ...will resume when the 3000i cools Unit will not stay in a Charge ON state Low and changing sun intensity PV connected to BAT external to controller Normal operation PV BAT must be separate for proper operation External connection prevents proper operation of current measurement system Charge status indicator ON but no output charge current Battery voltage greater than present charge voltage setpoin...

Страница 15: ...may float around a few 10ths of a volt LVD Load control not working correctly Auxiliary output not set for load control Output may have shut off due to low battery charge ON OFF thresholds set incorrectly Lighting control enabled Confirm out setting is set to Lod Load will shut off if battery voltage drops below OFF threshold default 11 5V Once shut off the load will not come back on until battery...

Страница 16: ...irs 3 This limited warranty does not apply to and future warranty shall become void for any product or part thereof damaged by a alteration disassembly or application of a foreign substance b repair or service not rendered by a BSE authorized repair facility c accident or abuse d corrosion e lightning or other act of God f operation or installation contrary to instructions pertaining to the produc...

Отзывы: