BLUE SKY SB3000i Скачать руководство пользователя страница 14

Blue Sky Energy 

 Solar Boost 3000i 

 

13

                                                                                                                                                                                                       Blue Sky Energy | USA | 

www.blueskyenergyinc.com

 

TROUBLESHOOTING GUIDE 

 

 If operational problems occur the single most important troubleshooting item is to be certain that battery voltage as 

measured on the battery terminals of the 3000i is the same as voltage measured on the batteries themselves within a 
few 10

ths

 of a volt at all times. If voltages are different there is a connection problem to the battery which often resides 

within the battery fuse or fuse holder. The fuse holder feeling warm or hot during operation is a sure sign of  a poor 
quality  or  failing  fuse  or  fuse  holder  which  must  be  corrected.  Once  proper  battery  voltage is confirmed the second 
most important item to check is PV voltage on the PV terminals of the 3000i. While PV voltage will vary greatly when 
the 3000i is in a Charge On state, the 3000i will not switch to a Charge ON state unless PV voltage is at least 0.3V higher 
than battery voltage with everything connected in the normal manner. 

 

SYMPTOM 

PROBABLE CAUSE 

ITEMS TO EXAMINE OR CORRECT 

Completely dead, 
display blank. 

No battery power. 
 
 
Display mode set to OFF. 

Battery disconnected, overly discharged, or connected reverse polarity. Battery powers 
3000i, not PV. Voltage present on the 3000i

’s battery terminals must be the same as actual 

battery voltage within a few 10

ths

 and at least 9 volts. 

Press Display Select to select display mode other than OFF. 

Display very dim. 

3000i in Charge Off state 

Normal operation, display automatically dims when 3000i is in Charge Off state even if 

Slave(s) are in charge on state causing Float/ Absorption LEDs’ to be on.

 

All display segments & 
LED indicators stuck 
on. 

PV connected reverse polarity. 
PV- connected to BAT- external to 
controller causing unexpected ground 
currents. 

Immediately correct polarity. 
PV- & BAT- must be separate for proper operation. External connection prevents proper 
operation. 

Unit will not switch to 
Charge ON state. 

No battery power. 
 
 
PV disconnected or low in voltage. 
 
 
PV reverse polarity. 
 
Microprocessor lockup. 
 
Over temperature shutdown. 

Battery disconnected, overly discharged, or connected reverse polarity. Battery powers 

3000i, not PV. Voltage present on the 3000i’s battery terminals must be the same as actua

battery voltage within a few 10

ths

 and at least 9 volts. 

PV voltage when connected to the 3000i must be at least 0.3V greater than battery voltage 
for 3000i to switch to Charge On State. 
 
Reverse PV will heat front panel & force all display segments & LE

D’s ON

 
Momentarily remove all power (battery & PV) to re-boot. 
 
Normal operation will resume when the 3000i cools. 

Unit will not stay in a 
Charge ON state. 

Low and changing sun intensity. 
 
PV- connected to BAT- external to 
controller. 

Normal operation. 
 
PV- & BAT- must be separate for proper operation. External connection prevents proper 
operation of current measurement system. 

Charge status 
indicator ON but no 
output charge current. 

Battery voltage greater than present 
charge voltage setpoint. 
 
 
Battery voltage too low. 
 
Poor connection to the battery. 
 
 
PV- connected to BAT- external to 
controller. 

Normal operation. Output is off due to high battery voltage which may be caused by other 
charging systems, or immediately following a switch to Float before battery voltage 
dropped and settled. 
 
Battery voltage must be at least 9 volts for the 3000i to operate. 
 
Voltage present on the 3000I

’s battery terminals must be the same as actual battery voltage 

within a few 10ths. Examine connections and fuse & fuse holder.  
 
PV- & BAT- must be separate for proper operation. External connection prevents proper 
operation of current measurement system. 

Charge OFF at high 
ambient temperature. 

System temporarily shuts down due to 
high internal temperature. 

Normal operation, improve ventilation or reduce PV power.  

Charge current is 
lower than expected.  

Battery is highly charged. 
 
 
User expectations too high. 
 
 
 
Worn out or very dissimilar PV modules 
Low sun intensity 
 
PV- connected to BAT- external to 
controller. 

Normal operation. Current is intentionally reduced in Absorption & Float to control battery 
voltage at setpoint. Maximum available charge current will only be seen when the 3000i is 
in Bulk. 

Even though the PV’s may be in full sun, clean, and with zero shading it

 is common to only 

see about 75 

 80% of total PV I

MP

. Note that the smallest amount of shade can cause a 

large reduction in charge current. Replace, or use as is. 
 

Atmospheric haze, PV’s dirty or shaded, sun low on horizon, etc.

 

 
 
PV- & BAT- must be separate for proper operation. External connection prevents proper 
operation of current measurement system. 

MPPT Current boost is 
less than expected 
 

PV maximum power voltage (V

MP

) is near 

battery voltage, leaving little extra power 
to be extracted 
 
 

PV’s hot

 

 
 
Worn out or dissimilar PV modules 

PV’s with low V

MP

. PV’s with V

MP

 

 

17V work best, PV’s with <36 cells tend to work poorly.

 

Excessive PV wiring voltage drop due to undersize wiring, poor connections etc. 
Battery is nearly charged and battery voltage is high. Output during MPPT operation is 

“constant power” such that higher battery voltage reduces charge current increase.

 

 
V

MP

 

and available power decrease with increasing PV cell temperature. Cooler PV’s will 

produce greater boost. It is normal for % increase to drop or even go to zero as PV 
temperature rises. 
Replace, use as is, or use different controller for different PV modules. 

 

Содержание SB3000i

Страница 1: ...RE OF THE FOLLOWING US PATENTS 6 111 391 6 204 645 Blue Sky Energy Inc 2017 430 0034 C FCC CFR 47 Part 15 Subpart B This device complies with part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operations CONFORMS TO EN 6...

Страница 2: ...ped Factory Default Settings 7 Changing Charge And Load Control Settings 7 Selecting PV Modules 8 Mounting 8 Battery and PV Wiring 9 Optional Battery Temperature Sensor 9 Auxiliary Output 10 Auxiliary Battery Charge 10 Load Controller 10 Dusk To Dawn Lighting Control 11 Battery PV Power Connect Disconnect Order 11 Connecting The Battery 11 Connecting PV Modules 11 Installing A Multi Controller Sys...

Страница 3: ...cid battery can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION a This unit is designed to charge 12 volt 6 cell flooded or sealed type lead acid chemistry batteries within the range of 20 to 2 000 amp hours Follow battery manuf...

Страница 4: ... to prevent unwanted current drain There is a 5 second turn on delay and a 45 second turn off delay The 3000i operates on battery power not PV power Insure that voltage on the battery terminals of the 3000i is always the same as actual battery voltage within a few 10ths of a volt and greater than 9 volts for proper operation Note that the front panel serves as a heatsink for power control devices ...

Страница 5: ...end to be higher under light load and lower under a heavier load Do not think of these voltage values as absolutes but rather as a broad brush indication of approximate battery charge level Voltage at a particular state of charge will vary with battery size age construction temperature and with the level of charge or discharge current Most battery manufacturers recommend not discharging below abou...

Страница 6: ...nt PV over current protection and not a normal mode of operation If the 3000i enters 30 amp or 22 amp current limit on a regular basis it is possible that excessive PV power is connected Confirm that the PV modules do not exceed ratings shown in the Selecting PV Modules section OPTIONAL TEMPERATURE COMPENSATION The charge voltage required by batteries changes with battery temperature Temperature c...

Страница 7: ...s use the front panel as a heatsink It is normal for the front panel to become quite warm to the touch when the 3000i is operating normally Front panel heating will be the greatest when the 3000i is processing either very high power or very low power When mounted to a vertical surface with good ventilation the 3000i can deliver full output in an ambient temperature of up to 45 C 113 F If an over t...

Страница 8: ...nd value of that setting Setting Range Setting Steps Description Setting Text Default Setting AbS 14 4 12 0V 17 0V 0 1V Absorption charge voltage Abt 2 0 0 0 10 0 hrs 0 5 hrs Absorption charge time FLt 13 2 12 0V 17 0V 0 1V Float charge voltage Set to oFF one step below 12 0 for 2 stage charge EqU 15 2 12 0V 17 0V 0 1V Equalize charge voltage Eqt 2 0 0 5 10 0 hrs 0 5 hrs Equalize charge time Norma...

Страница 9: ... boost performance When multiple controllers are used on the IPN Network each controller independently MPPT s their modules to their best Do not mix 36 cell and 60 cell modules on the same controller Select PV modules that do not exceed the maximum ratings shown below and preferably produce IMP of at least 3 5 amps 2 amps with 60 cell modules per 100 amp hours of battery capacity Voltage current a...

Страница 10: ...e two wire sizes larger than shown e g 8awg rather than 12awg for the wire section between the 3000i and the battery MAXIMUM CONDUCTOR PAIR LENGTH 3 VOLTAGE DROP WIRE GAUGE AWG 60 CELL MODULES 11 8AMP INPUT FEET METERS 36 CELL MODULES 24AMPS INPUT FEET METERS 12 AWG 17 9 5 5 5 3 1 6 10 AWG 28 5 8 7 8 5 2 6 8 AWG 45 3 13 8 13 5 4 1 6 AWG 71 2 21 7 21 4 6 5 4 AWG 114 1 34 8 34 0 10 4 TABLE 3 CAUTION...

Страница 11: ...ted or not CAUTION The auxiliary output CANNOT perform both auxiliary battery charge and load lighting functions at the same time DO NOT use the 20 amp Load terminal for auxiliary battery charge or the 3000i may be damaged in a manner that voids the warranty For clarity Figure 5 only shows additional wiring required for auxiliary output use and assumes basic system wiring shown in Figure 4 is comp...

Страница 12: ...timer If both timers are set to DISABLED factory default the lighting control feature is disabled If either the Post Dusk PSt or Pre Dawn PrE timers are set to a time value the lighting control feature is enabled When lighting control is enabled the Load output is controlled by both the normal LVD control function and the lighting control function such that whichever function wants the Load output...

Страница 13: ...n and the front panel may get hot quickly Should this occur immediately remove PV power and correct the fault INSTALLING A MULTI CONTROLLER SYSTEM USING THE IPN NETWORK The 3000i may also serve as an IPN Network Master controlling up to 7 remote IPN Network compatible Slaves Any Blue Sky Energy charge controller capable of operating as an IPN Network Slave may be used and as of this writing includ...

Страница 14: ...will resume when the 3000i cools Unit will not stay in a Charge ON state Low and changing sun intensity PV connected to BAT external to controller Normal operation PV BAT must be separate for proper operation External connection prevents proper operation of current measurement system Charge status indicator ON but no output charge current Battery voltage greater than present charge voltage setpoin...

Страница 15: ...may float around a few 10ths of a volt LVD Load control not working correctly Auxiliary output not set for load control Output may have shut off due to low battery charge ON OFF thresholds set incorrectly Lighting control enabled Confirm out setting is set to Lod Load will shut off if battery voltage drops below OFF threshold default 11 5V Once shut off the load will not come back on until battery...

Страница 16: ...irs 3 This limited warranty does not apply to and future warranty shall become void for any product or part thereof damaged by a alteration disassembly or application of a foreign substance b repair or service not rendered by a BSE authorized repair facility c accident or abuse d corrosion e lightning or other act of God f operation or installation contrary to instructions pertaining to the produc...

Отзывы: